Air-ConditionersTECHNICAL & SERVICE MANUALModelsPEFY-P06NMSU-E, PEFY-P08NMSU-EPEFY-P12NMSU-E, PEFY-P15NMSU-EPEFY-P18NMSU-E, PEFY-P24NMSU-EFor use
[ II Components and Functions ] - 3 -HWE08010 GB(2) Remote Controller DisplayA Current time/Timer time I Louver swingB Centralized control indicator
[ III Specfications ] - 4 -HWE08010 GBIII Specfications[1] Specifications1. SpecficationsModel PEFY-P06NMSU-E PEFY-P08NMSU-E PEFY-P12NMSU-E PEFY-P15N
[ III Specfications ]- 5 -HWE08010 GBModel PEFY-P18NMSU-E PEFY-P24NMSU-EPower source 1-phase 208/230V 60HzCooling capacity *1 BTU / h 18,000 24,0
[ III Specfications ] - 6 -HWE08010 GB2. Electrical component specificationsComponent Sym-bolPEFY-P06NMSU-E PEFY-P08NMSU-E PEFY-P12NMSU-ERoom tempera
[ IV Outlines and Dimensions ] - 7 -HWE08010 GBIV Outlines and Dimensions[1] Outlines and Dimensions1. PEFY-P06,08,12,15,18,24NMSU-Emm(in.)(35-7/16)(
[ V Wiring Diagram ]- 8 -HWE08010 GBV Wiring Diagram[1] Wiring Diagram1. PEFY-P06,08,12,15,18,24NMSU-E8765432143211~MM4231M1324 12 145676531432113512
[ VI Refrigerant System Diagram ] - 9 -HWE08010 GBVI Refrigerant System Diagram[1] Refrigerant system diagram(A) Gas pipe thermistor TH23(B) Gas pipe
[ VII Microprocessor Control ]- 10 -HWE08010 GBVII Microprocessor Control[1] Microprocessor Control1. Cool operation1. Termoregulating function(1) Th
[ VII Microprocessor Control ] - 11 -HWE08010 GBIn the air : Detected that the float switch is OFF for 15 seconds.2. Dry operation1. Termoregulating
[ VII Microprocessor Control ]- 12 -HWE08010 GBRemote controller setting is not acceptable.3. Drain pump(1) Same control as COOL operation3. Fan ope
iiHWE08010 GBSafety PrecautionsRead before installation and performing electrical workSymbol explanationsThoroughly read the following safety precaut
[ VII Microprocessor Control ] - 13 -HWE08010 GB4. Heat operation1. Termoregulating function(1) Thermoregulating function (Function to prevent restar
[ VII Microprocessor Control ]- 14 -HWE08010 GBThis control is same for the model without auxiliary heater.(4) Thermo OFF modeWhen the thermoregulat
[ VII Microprocessor Control ] - 15 -HWE08010 GB4. HEAT mode(1) Same control as heat operationThe value "3°F" is modifiable from 1.8°F to 9
[ VII Microprocessor Control ]- 16 -HWE08010 GB(1) On the ducted model units (except the Fresh air intake type), turning on the heater with the fan s
[ VII Microprocessor Control ] - 17 -HWE08010 GBReference (not applicable to the ducted models)This is applicable only to the R410A series. Make the
[ VII Microprocessor Control ]- 18 -HWE08010 GB2) PEFY-P-NMHU-E, PDFY-P-NMU-E and other modelsFor relay X use the specifications given below Opera
[ VIII Troubleshooting ] - 19 -HWE08010 GBVIII Troubleshooting[1] Troubleshooting1. Check methods1. Component and check points(1) ThermistorRoom te
[ VIII Troubleshooting ]- 20 -HWE08010 GB1) Summary of linear expansion valve (LEV) operationThe LEV is operated by a stepping motor, which operat
[ VIII Troubleshooting ] - 21 -HWE08010 GB2) LEV operationWhen the power is turned on, a pulse signal of 2200 pulses is output (valve closure sign
[ VIII Troubleshooting ]- 22 -HWE08010 GB(4) Drain-up mechanismMeasure the resistance between the terminals with a tester. (coil temperature 20°C[68°
iiHWE08010 GBPrecautions for handling units for use with R410AWARNINGKeep electrical parts away from water.Wet electrical parts pose a risk of electri
[ VIII Troubleshooting ] - 23 -HWE08010 GB2. DC fan motor (fan motor/indoor control board)1. CAUTION A high voltage is applied to the connector for
[ VIII Troubleshooting ]- 24 -HWE08010 GB3. Address switch settingMake sure that power to the unit is turned off.1. When using an ME remote controll
[ VIII Troubleshooting ] - 25 -HWE08010 GB4. Voltage test points on the control board1. PEFY-P06,08,12,15,18,24NMSU-EFuse Fuse(AC 250V 6.3A)CND Power
[ VIII Troubleshooting ]- 26 -HWE08010 GB5. Dipswitch setting (Factory setting)1. Function setting(1) SW11) Adress board(2) SW3*1 Please don't
[ VIII Troubleshooting ] - 27 -HWE08010 GB2. Capacity code setting(1) SW21) Indoor control boardDipswitch settings must be made while the unit is s
[ VIII Troubleshooting ]- 28 -HWE08010 GB6. Connection No. setting(1) SW14 (Rotary switch) This switch is used when the unit connected to an R2 seri
[ IX Disassembly Procedure ] - 29 -HWE08010 GBIX Disassembly Procedure[1] Disassembly Procedure1. Control boxExercise caution when removing heavy par
[ IX Disassembly Procedure ]- 30 -HWE08010 GB2. Thermistor (Intake air)Exercise caution when removing heavy parts.1. Remove the control box cover ac
[ IX Disassembly Procedure ] - 31 -HWE08010 GB3. DrainpanExercise caution when removing heavy parts.1. Removing the filter and the bottom plate(1) P
[ IX Disassembly Procedure ]- 32 -HWE08010 GB4. Thermistor (Gas pipe) (Liquid pipe)Exercise caution when removing heavy parts.1. Remove the drain pa
iiiiiiHWE08010 GBPrecautions for PAC-YU25HT (Optional parts)WARNINGStop the operation if any malfunction occurs.If malfunction occurs (burning smell,
[ IX Disassembly Procedure ] - 33 -HWE08010 GB5. Fan and fan motorExercise caution when removing heavy parts.1. Removing the filter and the bottom p
[ IX Disassembly Procedure ]- 34 -HWE08010 GB6. BearingP15, P18, P24 models only.Exercise caution when removing heavy parts.1. Removeing the bearing
[ IX Disassembly Procedure ] - 35 -HWE08010 GB7. Heat exchangerExercise caution when removing heavy parts.1. Remove the drain pan according to the p
Jul. 2008 HWE08010Printed in JapanNew publication, effective Jul. 2008Specifications subject to change without notice
ivHWE08010 GB
CONTENTSHWE08010 GBIFeatures[1] Features...
HWE08010 GB
[ I Features ] - 1 -HWE08010 GBI Features[1] FeaturesModel Cooling capacity/Heating capacityBTU/h kWPEFY-P06NMSU-E 6000/6700 1.8/2.0PEFY-P08NMSU-E 80
[ II Components and Functions ]- 2 -HWE08010 GBII Components an d Functi ons[1] Components and Functions1. Indoor (Main) Unit2. Remote Controller[PA