Item Description
Group setting
Individual setting
Time & date setting
Alarm history
Demand control
Emergency stop
Power restoration control
Power failure compensation
No.
1
2
4
5
6
7
8
9
Registers controlled air-conditioners (max. 64 units) to max. 16 groups.
Sets air-conditioners which are subject to the control of SC-SL2N-E, but are not
registered to any group.
Sets all air-conditioners connected to this unit at “Stop” and “Center” with an ex-
ternal emergency signal. As the emergency signal is cancelled, the center/remote
setting is returned to original state but all units stay “Stopped”
The group setting, individual setting, program timer setting, holiday setting, exter-
nal timer setting, demand setting and operating condition (RUN/STOP, operating
mode, temperature setting, Center/Remote, remote controller permission/prohibi-
tion and airflow volume) are retained regardless of the length of power failure,
The clock time is compensated if the power interruption is not longer than 48
hours. If the current time is not displayed after the power restoration following a
power interruption exceeding 48 hours, set again the current time. Since the clock
time is not retained at the power restoration after a power interruption exceeding
48 hours, the power restoration control in Item No. (9) (a) does not operate.
Allows changing the power restoration process setting.
Program timer preferred: When SW1 and SW2 are turned ON. RUN/STOP and
setting temperature returns to the program timer just before the time of power
restoration on the day when the power supply is restored, or other states (opera-
tion mode, etc) return automatically with the priority given to the states before
the power failure (See ).
When no program timer is set before the power restoration on the day of power
restoration, it is restored with the priority given to the states before the power
failure (See ).
State before power failure preferred: When SW1 is turned ON and SW2 is
turned OFF. Each indoor unit returns automatically to the state before the pow-
er failure.
Any indoor unit running before the power failure starts its operation.
No power restoration processing: When SW1 and SW2 are turned OFF. SC-
SL2N-E does not perform timer the power restoration processing upon restora-
tion of the power supply.
Sets the clock used for program timer or other.
•Year/Month/Date/Hour (24-hour basis) /Minute
Changes preset air-conditioners to “Fan” and “Center” with external demand sig-
nals. When the demand signal is cancelled, it returns to the state just before enter-
ing the demand control (operation mode and center/remote setting).
Displays the error history of around. 100 cases for each air-conditioner.
(5) Administration and control
(6) Outline drawing
01
09
02
10
03
11
04
12
05
13
06
14
07
15
169
215
25
35
120
87
Resin color: Pearl white
(close to Munsell N-8.5)
(4) Program setting
Operation program can be set in the unit of group. It is possible to register the ON/OFF time or ON time + Temperature setting at
4 times a day. Operation time can be designated in the unit of minute.