Mitsubishi FDCP224HKXE2B User Manual

Browse online or download User Manual for Split-system air conditioners Mitsubishi FDCP224HKXE2B. ERROR CODES – R410A

  • Download
  • Add to my manuals
  • Print
  • Page
    / 5
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
ERROR CODES – R410A
Black = All R410A
Red = FD Split 1, 2 Series R410A
Blue = KX4 & KXR4 Series R410A
(does not cover SRK & SCM MODELS)
Indoor Circuit Board Outdoor Circuit Board
Error
Code
Red LED
Green
LED
Red LED Green LED
Details of Fault
Stays Off
Keeps
Flashing
Stays Off
Keeps
Flashing
Normal operation.
Stays Off Stays Off Stays Off Stays Off
No mains power detected [power off or power
failure].
L phase wire is open circuit.
No
indication
Flashes 3
times
Keeps
Flashing
Stays Off
Keeps
Flashing
Remote controller wires - X & Y connections are
reversed.
Remote controller wires - Y & Z connections are
reversed.
Remote controller wiring is open circuit. (X wire
broken - a beep is produced and no indication is
made. Z wire broken -no beep and no indication).
LCD
Flashes
continuou
sly or Off
Stays Off
Keeps
Flashing
Flashes
Twice
Keeps
Flashing
Open Circuit or poor indoor/outdoor interconnecting
wiring
Stays Off
Off or On
continuousl
y
Stays Off
Keeps
Flashing
Indoor circuit board or CPU failure.
Off or On
continuou
sly
Off or On
continuousl
y
Stays Off
Keeps
Flashing
Indoor circuit board or CPU failure.
Stays Off
Keeps
Flashing
Stays Off
Keeps
Flashing
In group control, power supply to at least one indoor
unit off
Remote controller wire Y is open circuit
Remote controller wires X and Y are reversed
Faulty Indoor or Remote controller PCB
Electrical noise interference
Stays Off
Keeps
Flashing
Stays Off
Keeps
Flashing
Remote controller wiring connected to A and B
A and B wiring connected in closed loop
Indoor unit PCB processor runs away
E1
Flashes 3
times
Keeps
Flashing
Stays Off
Keeps
Flashing
Remote controller wiring open circuit
Technical Support
Spares & Warranty
01359 272211
Mitsubishi Heavy Industries Air Conditioning Error Codes – R410A Systems
Page view 0
1 2 3 4 5

Summary of Contents

Page 1 - ERROR CODES – R410A

ERROR CODES – R410A Black = All R410A Red = FD Split 1, 2 Series R410A Blue = KX4 & KXR4 Series R410A (does not cover S

Page 2

E2 Flashes once Keeps Flashing Stays Off Keeps Flashing • Duplication of indoor unit address. • More than 49 indoor units are connected on a network

Page 3

E12 Flashes once Keeps Flashing Stays Off Keeps Flashing • One or more units (indoor or outdoor) are still addressed at 48 or 49 [factory setting] •

Page 4

Stays Off Keeps Flashing Flashes Once Keeps Flashing • Outdoor unit heat exchanger sensor [ThOR] defective (resistance is open circuit). • Poor conn

Page 5

E46 Stays Off Keeps Flashing Off Keeps Flashing • There is a conflict of address settings. • A combination of: automatic / manual / remote control

Comments to this Manuals