SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES ··································· 2
2. PART NAMES AND FUNCTIONS ····················· 3
3. SPECIFICATION ················································ 4
4. OUTLINES AND DIMENSIONS ························ 8
5. WIRING DIAGRAM ·········································· 10
6. REFRIGERANT SYSTEM DIAGRAM ············· 15
7. DATA ································································ 18
8. ACTUATOR CONTROL ··································· 30
9. SERVICE FUNCTIONS ··································· 31
10. TROUBLESHOOTING ····································· 31
11. DISASSEMBLY INSTRUCTIONS ···················· 49
Models
MUZ-GE09NA
MUZ-GE12NA
MUZ-GE15NA
MUZ-GE18NA
MUZ-GE24NA
MUY-GE09NA
MUY-GE12NA
MUY-GE15NA
MUY-GE18NA
MUY-GE24NA
SPLIT-TYPE AIR CONDITIONERS
OUTDOOR UNIT
Indoor unit service manual
MSZ-GE•NA MSY-GE•NA Series (OBH548)
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
TM
HFC
utilized
R410A
No. OBH549
REVISED EDITION-B
PARTS CATALOG (OBB549)
Revision B:
Descriptions regarding the outdoor fan motor
have been corrected.
Please void OBH549 REVISED EDITION-A.
MUZ-GE09/12/15NA
MUY-GE09/12/15NA
Page view 0
1 2 3 4 5 6 ... 57 58

Summary of Contents

Page 1 - SERVICE MANUAL

SERVICE MANUALCONTENTS1. TECHNICAL CHANGES ··································· 22. PART NAMES AND FUNCTIONS ····················· 33. SPECIFICATION ··

Page 2 - TECHNICAL CHANGES

10MUZ-GE09NA MUZ-GE12NA5WIRING DIAGRAMMUY-GE09NA MUY-GE12NA

Page 4 - SPECIFICATION

12MUZ-GE18NAMUY-GE18NA

Page 6

14MUY-GE24NA

Page 7 - Test condition

15Unit: inchMUZ-GE09NA MUY-GE09NAOutdoorheatexchangerFlared connectionDefrostthermistorRT61(MUZ)DischargetemperaturethermistorRT62Flared connectionSt

Page 8 - OUTLINES AND DIMENSIONS

16MUZ-GE18NA MUY-GE18NAOutdoorheatexchangerFlared connectionDefrostthermistorRT61(MUZ)DischargetemperaturethermistorRT62Flared connectionStop valve(w

Page 9 - REQUIRED SPACE

17Max. Length AMax. HeightdifferenceBIndoorunitOutdoor unitMAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCEModel Refrigerant pipin

Page 10 - WIRING DIAGRAM

18 Model Indoor air Outdoor intake air DB temperature (˚F) IWB (˚F) 75 85 95 105 115TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC MUZ-GE09NA

Page 11 - MUY-GE15NA

193) HEATING CAPACITY (MUZ)Model Indoor air Outdoor intake air WB temperature (˚F) IDB (˚F) 5 152535434555TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC T

Page 12 - MUY-GE18NA

2MUZ-GE09NAMUZ-GE12NAMUZ-GE15NAMUZ-GE18NAMUZ-GE24NAMUY-GE09NAMUY-GE12NAMUY-GE15NAMUY-GE18NAMUY-GE24NA1. New model1TECHNICAL CHANGESRevision B:• Descri

Page 13 - MUZ-GE24NA

20757065Indoor intake air DB temperature (°F)= 413 CFMAirflow155253545556570Outdoor intake air WB temperature (°F)0.40.60.81.01.1Total power consumpti

Page 14 - MUY-GE24NA

21This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships between frequency and capac

Page 15 - REFRIGERANT SYSTEM DIAGRAM

22MUZ-GE15NA MUY-GE15NA(PSIG) (PSIG)68 70 75 80 85 90 95 100105(°F)1201401601802006870 75 80 85 9095100 105(°F)280320360400440Condensing pressure8680

Page 16 - × 1-31/32

235 15253545556575(°F) 5 15253545556575(°F)6085110135160185210220245270295320345370Indoor DB temperature (°F)Condensing pressureOutdoor ambient temper

Page 17

24MUZ-GE18NA5 15253545556575(°F)60851101351601852105 15253545556575(°F)300325350375400425450475500Indoor DB temperature (°F)Condensing pressureOutdoor

Page 18

257-4. STANDARD OPERATION DATAModelMSZ-GE09NAMSY-GE09NAMSZ-GE09NAMSZ-GE12NAMSY-GE12NAMSZ-GE12NAItem Unit Cooling Heating Cooling HeatingTotalCapacity

Page 19 - Capacity correction factors

26ModelMSZ-GE15NAMSY-GE15NAMSZ-GE15NAMSZ-GE18NAMSY-GE18NAMSZ-GE18NAItem Unit Cooling Heating Cooling HeatingTotalCapacity Btu/h 14,000 18,000 17,200 2

Page 20 - Heating capacity (

27ModelMSZ-GE24NAMSY-GE24NAMSZ-GE24NAItem Unit Cooling HeatingTotalCapacity Btu/h 22,500 27,600SHF - 0.75 —Input kW 1.800 2.340Rated frequency Hz 66.5

Page 21 - Indoor DB temperature (°F)

287-5. CAPACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCYCapacity correction factorsInput correction factorsInput correction factorsCapacity c

Page 22

297-6. HOW TO OPERATE FIXED-FREQUENCY OPERATION (Test run operation) 1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL: Press once,

Page 23 - (°F) 5 15253545556575(°F)

3MUZ-GE09NA MUZ-GE12NA MUZ-GE15NAMUY-GE09NA MUY-GE12NA MUY-GE15NAAir outletDrain outletPipingDrain hoseAir inlet(back and side)MUZ-GE18NA MUY-GE1

Page 24 - Suction pressure

30MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NAMUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA8-2. R.V. COIL CONTROL (MUZ)Heat

Page 25 - 7-4. STANDARD OPERATION DATA

319-1. CHANGE IN DEFROST SETTING (MUZ) Changing defrost finish temperature <JS> To change the defrost finish temperature, cut/solder the JS wi

Page 26

32Outline of the functionThis air conditioner can memorize the abnormal condition which has occurred once.Even though LED indication listed on the tro

Page 27

33 2. Flow chart of the detailed outdoor unit failure mode recall function 2.Blinking pattern when outdoor unit is abnormal:ONOFFNo beepBeepsRepe

Page 28

34 3. Outdoor unit failure mode tableOPERATION INDICATORupper lamp(Indoor unit) Abnormal point (Failure mode / protection) LED indication(Outdoor P

Page 29 - Heating total input

3510-3. TROUBLESHOOTING CHECK TABLENo. Symptom LED indication Abnormal point/ Condition Condition Remedy1Outdoor unit does not oper-ate. 1-time fl ash

Page 30 - ACTUATOR CONTROL

3610-4. TROUBLE CRITERION OF MAIN PARTSMUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NAMUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-G

Page 31 - SERVICE FUNCTIONS

3710-5. TROUBLESHOOTING FLOWAre the voltages balanced?Disconnect the connector between compressor and the intelligent power module (IPM).Replace the i

Page 32 - MSY-GE24NA

38 F Check of compressor start failure D Check of compressor winding E Check of compressor operation time● Disconnect the connector between the com

Page 33 - Operational procedure

39Is the resistance of thermistor normal? (Refer to 10-6.1.)Reconnect the connector of thermistor.Turn ON the power supply and press EMERGENCY OPERATI

Page 34

4Outdoor unit model MUZ-GE09NA MUY-GE09NA MUZ-GE12NA MUY-GE12NA Capacity Rated (Minimum~Maximum) Cooling 1 Btu/h9,000( 3,800 ~ 12,200 )9,000( 3,800 ~

Page 35

40 I Check of outdoor fan motorIs the resistance between each ter-minal of outdoor fan motor normal? (Refer to 10-4.)Disconnect the connectors CN931

Page 36

41 J Check of power supplyIs there voltage 208/230 VAC between the indoor terminal block S1 and S2?NoYesReplace the indoor electronic control P.C. bo

Page 37 - C Check of compressor

42Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor

Page 38

43 L Check of inverter P.C. boardCheck the outdoor fan motor. (Refer to 10-5. .)Is the fuse (F901) blown on the in-verter P.C. board?Check the connec

Page 39 - H Check of R.V. coil

44 M How to check miswiring and serial signal errorTurn OFF inverter-controlled lighting equipment.Turn OFF the power supply and then turn ON again.P

Page 40

45 N Electromagnetic noise enters into TV sets or radiosYesIs the unit grounded?NoGround the unit.YesIs the distance between the antennas and the ind

Page 41 - MUZ-GE24NA MUY-GE24NA

46-4 14 32 50 68 86 1040102030405060708090100Temperature(°F)Defrost thermistor(RT61) (MUZ)Ambient temperature thermistor(RT65)Outdoor heat exchanger t

Page 42

47-4 14 32 50 68 86 1040102030405060708090100Temperature(°F)Defrost thermistor(RT61) (MUZ)Ambient temperature thermistor(RT65)Outdoor heat exchanger t

Page 43

48-4 14 32 50 68 86 1040102030405060708090100Temperature(°F)Defrost thermistor(RT61) (MUZ)Ambient temperature thermistor(RT65)Outdoor heat exchanger t

Page 44

4911-1. MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUY-GE09NA MUY-GE12NA MUY-GE15NA NOTE: Turn OFF power supply before disassembly.OPERATING PROCEDURE PHOT

Page 45

5Outdoor unit model MUZ-GE15NA MUY-GE15NA MUZ-GE18NA MUY-GE18NA Capacity Rated (Minimum~Maximum) Cooling 1 Btu/h14,000( 3,100 ~ 18,200 )14,000( 3,100

Page 46

50OPERATING PROCEDUREPHOTOS2. Removing the inverter assembly, inverter P.C. board(1) Remove the cabinet and panels. (Refer to 1.)(2) Disconnect the le

Page 47 - MUZ-GE18NA MUY-GE18NA

51OPERATING PROCEDUREPHOTOS4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger tempera-ture thermistor and am

Page 48

5211-2. MUZ-GE18NA MUY-GE18NANOTE: Turn OFF power supply before disassembly.OPERATING PROCEDUREPHOTOS1. Removing the cabinet(1) Remove the screws of

Page 49 - DISASSEMBLY INSTRUCTIONS

53OPERATING PROCEDUREPHOTOS2. Removing the inverter assembly, inverter P.C. board(1) Remove the cabinet and panels. (Refer to 1.)(2) Disconnect the le

Page 50 - OPERATING PROCEDURE

54Ambient tem-peraturethermistorOutdoor heat exchanger tempera-ture thermistorDefrost thermistorOPERATING PROCEDURE PHOTOS4. Removing the discharge te

Page 51

5511-3. MUZ-GE24NA MUY-GE24NANOTE: Turn OFF power supply before disassembly.OPERATING PROCEDURE PHOTOS1. Removing the cabinet(1) Remove the screws of

Page 52 - 11-2. MUZ-GE18NA MUY-GE18NA

56OPERATING PROCEDUREPHOTOS2. Removing the inverter assembly, inverter P.C. board(1) Remove the cabinet and panels. (Refer to 1.)(2) Disconnect the le

Page 53

57OPERATING PROCEDURE PHOTOS4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger tempera-ture thermistor and a

Page 54 - OPERATING PROCEDURE PHOTOS

HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN© Copyright 2009 MITSUBISHI ELECTRIC CO.,LTDDistributed in Dec. 2010. No

Page 55 - 11-3. MUZ-GE24NA MUY-GE24NA

6Outdoor unit model MUZ-GE24NA MUY-GE24NACapacity Rated (Minimum~Maximum) Cooling 1 Btu/h22,500(8,200 ~ 31,400)22,500(8,200 ~ 31,400)Heating 47 1 Btu

Page 56

7Test conditionARI Mode Test Indoor air condition (°F) Outdoor air condition (°F)Dry bulb Wet bulb Dry bulb Wet bulbSEER (Cooling) "A-2" Co

Page 57

8Unit: inchMUZ-GE09NA MUZ-GE12NA MUZ-GE15NAMUY-GE09NA MUY-GE12NA MUY-GE15NALiquid pipe :1/4 (flared)Gas pipe :3/8 (flared) (GE09/12) 1/2 (flared

Page 58

916-7/161-9/161-5/8Drain hole6-7/819-11/16132Air inAir out2-holes 13/32 13/1614-3/1633-1/164-5/163-3/1634-5/817-25/32Service panel3-29/326-1/27-11/1