EnglishDeutschFrançaisNederlandsEspañolItalianoΕλληνικάPortuguêsDanskSvenskaTürkçeРусскийINSTALLATION MANUALFor safe and correct use, read this manual
1010. System control (Fig. 10-1)* Set the refrigerant address using the DIP switch of the outdoor unit.(1) Wiring from the Remote ControlThis wire i
Please be sure to put the contact address/telephone number on this manual before handing it to the customer.This product is designed and intended for
21.2. Before installation (relocation) Caution:• Be extremely careful when transporting the units. Two or more persons are needed to handle the unit
32. Installation location1. Safety precautions1.3. Before electric work Caution:• Be sure to install circuit breakers. If not installed, electric
42. Installation location2.4. Ventilation and service space2.4.1. Windy location installationWhen installing the outdoor unit on a rooftop or other
54. Installing the refrigerant piping(A) Flare cutting dimensions(B) Flare nut tightening torqueTable 1 (Fig. 4-2)Copper pipe O.D.(mm)A (mm)Flare too
64. Installing the refrigerant piping4.3. Refrigerant piping (Fig. 4-3)n For RP35, 50Remove the service panel (D) (one screw).n For RP60-140Remove
74.7. Precautions when reusing existing R22 refrigerant pipes• Refertotheowchartbelowtodetermineiftheexistingpipescanbeusedandifit
86. Electrical workFig. 6-1Fig. 6-2n RP60-140n RP35, 50V(A) Earth terminal(B) Terminal block(C) Clamp(D) Service panel(E) Wire the cables so t
97.1. Before test run► After completing installation and the wiring and piping of the indoor and outdoor units, check for refrigerant leakage, loosen