SERVICE MANUAL
AIR TO WATER HEAT PUMP
No. OCH419
CONTENTS
1. SAFETY PRECAUTION
..........................................
2
2. SPECIFICATIONS
.....................................................
4
3. DATA
.............................................................................
5
4. OUTLINES AND DIMENSIONS
............................
7
5. WIRING DIAGRAM
...................................................
8
6. WIRING SPECIFICATIONS
....................................
9
7. REFRIGERANT SYSTEM DIAGRAM
...................
10
8. TROUBLESHOOTING
...........................................
11
9. DISASSEMBLY PROCEDURE
...........................
38
August 2007
Note:
This manual describes only
service data of PUHZ-W90VHA.
RoHS compliant products have
<G> mark on the spec name plate.
R410A
[model name]
PUHZ-W90VHA
[Service Ref.]
PUHZ-W90VHA
PUHZ-W90VHA
PARTS CATALOG (OCB419)
Page view 0
1 2 3 4 5 6 ... 44 45

Summary of Contents

Page 1 - PUHZ-W90VHA

SERVICE MANUALAIR TO WATER HEAT PUMPNo. OCH419 CONTENTS 1. SAFETY PRECAUTION...2 2. SPECIFICATIONS...

Page 2 - SAFETY PRECAUTION

10REFRIGERANT SYSTEM DIAGRAM7DistributorTH7Strainer(#100) Strainer(#100)ReceiverLEV-BTH6TH32Plate HEXWater INWater OUTStrainer(#100)TH3CHECK/VCHECK/VC

Page 3 - [3] Service tools

11TROUBLESHOOTING8Unit conditions at serviceError codeActions to be taken for service (summary)The trouble is reoccurring.DisplayedNot displayedJudge

Page 4 - SPECIFICATIONS

128-3. SELF-DIAGNOSIS ACTION TABLE<Abnormalities detected when the power is turned on>Error CodeAbnormal point and detection method CaseJudgment

Page 5 - CONTINUOUS

13<Abnormalities detected while unit is operating>Error CodeAbnormal point and detection method Judgment and actionU1High pressure (High-pressur

Page 6 - 3-2. STANDARD OPERATION DATA

14ThermistorsOpen detection Short detectionSymbolNameTH3TH6TH7TH8– 40 or below– 40 or below– 40 or below– 40 or below– 35 or below90 or above90

Page 7 - OUTLINES AND DIMENSIONS

15Error CodeAbnormal point and detection method CaseJudgment and actionU7Too low superheat due to low discharge temperatureAbnormal if discharge super

Page 8 - WIRING DIAGRAM5

16Error CodeAbnormal point and detection method Judgment and actionCaseUHCurrent sensor error or input current error·Abnormal if current sensor detect

Page 9 - WIRING SPECIFICATIONS6

17Error CodeAbnormal point and detection method Judgment and actionCaseP6Freezing/overheating protection is working(1)Freezing protection <Cooling

Page 10 - REFRIGERANT SYSTEM DIAGRAM7

18Error CodeAbnormal point and detection method Judgment and actionCasePEInlet water temperatureAbnormal if the following conditions aredetected for c

Page 11 - TROUBLESHOOTING8

198-4. HOW TO CHECK THE PARTS PUHZ-W90VHA123456MParts nameCheck pointsDisconnect the connector then measure the resistance using a tester. (At t

Page 12

2SAFETY PRECAUTION1Cautions for units utilizing refrigerant R410A1-2. CAUTIONS RELATED TO NEW REFRIGERANT1-1. ALWAYS OBSERVE FOR SAFETYBefore obtainin

Page 13

20Notes · High voltage is applied to the connector (CNF1) for the fan motor. Give attention to the service. · Do not pull out the connector (CNF1) of

Page 14

218-5. HOW TO CHECK THE COMPONENTS<Thermistor feature chart>Low temperature thermistors• Thermistor <Liquid pipe> (TH3)• Thermistor <Pl

Page 15

22Low temperature thermistor• Thermistor <Inlet water> (TH32) 0 15k10 9.6k20 6.3k25 5.1k30 4.2k40 2.9kThermistor R0 = 15k ± 2.5%B

Page 16 -  Malfunction of water pump

23<Output pulse signal and the valve operation>(2) Linear expansion valve operationOpenExtra tightning (about 32 pulse)Pulse number500 pulseO

Page 17 - 63HS-TH322and

24Main bodyLead wireStopperCoil(3) How to attach and detach the coil of linear expansion valve<Composition>Linear expansion valve is separable i

Page 18

258-6. TEST POINT DIAGRAMOutdoor controller circuit boardCNSNot usedCNAC to : Power supplyfor outdoor controller circuit board(220V-240V AC) to :

Page 19 - PUHZ-W90VHA

26CNAC1, CNAC2220-240V ACConnect to the out-door controller cir-cuit board (CNAC).EIConnect to the earth.LI, NIVoltage of 220-240V AC is input. Connec

Page 20

27Outdoor power circuit boardTABP1Connect toACTM+TABP2Connect to the ACTMCN4Connect to the outdoor controller circuit board (CN4)CN2Connect to the out

Page 21

28Interface circuit boardCNIF3Input signalConnect to theterminal block(TB2, TB3)CNIF1Connect to the outdoor controller circuit boardCNIF2Connect to th

Page 22 - Resistance (k)

29Active filter module(ACTM)—Connect to the outdoor power circuit board (TABN1)L1, L2Connect to the DCL (Reactor)+Connect to the outdoor power circuit

Page 23

331-3. CAUTIONS FOR REFRIGERANT PIPING WORKTools for R410A (The following table shows whether conventional tools can be used or not.)Gauge manifoldCha

Page 24 - <Composition>

308-7. OUTDOOR UNIT OPERATION MONITOR FUNCTIONSW2 setting1ON23456Display detailExplanation for display UnitOperation indicator SW2 : Indicator ch

Page 25 - (when operated)

31SW2 setting1ON23456Display detailExplanation for display UnitPipe temperature / Liquid(TH3)– 40~90– 40~90(When the coil thermistor detects 0 or bel

Page 26

32SW2 setting1ON23456Display detailExplanation for display UnitPipe temperature / Liquid(TH3) when error occured.– 40~90– 40~90(When the coil thermist

Page 27 - Outdoor power circuit board

33SW2 settingDisplay detailExplanation for displayUnit1ON23456Plate HEX liquid pipe temperature(TH6)– 39~88– 39~88(When the temperature is 0 or less

Page 28 - Interface circuit board

340.1 AInput current of outdoor unit0~5000~500(When it is 100 or more, hundreds digit, tens digit and ones digit are displayed by turns.)PulseLEV-B op

Page 29 - Active filter module(ACTM)

35SW2 settingDisplay detailExplanation for display UnitOperation frequency when error occured.0~2250~225(When it is 100Hz or more, hundreds digit, ten

Page 30 - 1 second

36SW2 settingDisplay detailExplanation for display UnitSub cool (SC) when error occured. 0~130 Cooling:SC = T63HS-TH3 Heating:SC = T63HS-TH60~130

Page 31 - Explanation for display Unit

378-8. FUNCTION OF SWITCHESSwitchFunctionSelectionInitial setting* Function detailsEffective timing (SW1, 8) / Note (SW6)mark No. ON (with) OFF (witho

Page 32

38DISASSEMBLY PROCEDURE9OPERATING PROCEDUREPUHZ-W90VHA 1. Removing the service panel and top panel(1) Remove 3 screws (5x10) and slide the hook on th

Page 33 - Explanation for display

3939OPERATING PROCEDUREPHOTOS&ILLUSTRATION 4. Removing the thermistor <Plate HEX Liquid> (TH6)(1) Remove the service panel. (See figure 1.)

Page 34

4SPECIFICATIONS2Power supply Phase㱢Voltage VnoitidnocgnitarepolanimoNzHycneuqerFHeating Capacity kW Heating(A2/W35)(A2/W35) 2+)blub-yrD(erutarepmetria

Page 35

40OPERATING PROCEDUREPHOTOS&ILLUSTRATION 8. Removing the solenoid valve coil <Four-way valve> (21S4) linear expansion valve coil (LEV (A),

Page 36 - Compressor frequency control

41OPERATING PROCEDUREPHOTOS&ILLUSTRATION 11. Removing the bypass valve (1) Remove the service panel. (See figure 1.) (2) Remove the top panel. (S

Page 37 - 1=ON, 0=OFF

42OPERATING PROCEDUREPHOTOS&ILLUSTRATION 14. Removing the compressor (MC) (1) Remove the service panel. (See figure 1.) (2) Remove the top panel

Page 38 - DISASSEMBLY PROCEDURE

43OPERATING PROCEDUREPHOTOS&ILLUSTRATION 17. Removing the interface circuit board (I.F.) : Figure 2 (1) Remove 2 Interface board cover fixing scr

Page 39 - PHOTOS&ILLUSTRATION

HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN©Copyright 2007 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.Distributed in

Page 40

  

Page 41

5DATA31.5m1mMICROPHONEUNITGROUND90807060504030201063 125 250 500 1000 2000 4000 8000APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISENC-60NC-50NC-40NC

Page 42

63-2. STANDARD OPERATION DATAMode Cooling (A35/W7) Heating (A7/W35)TotalCapacity W 7,100 9,000Input kW 3.55 2.31Electrical circuitOutdoor unit PUHZ-W9

Page 43

77OUTLINES AND DIMENSIONS4PUHZ-W90VHAHandle for movingSide Air Intake330175 600 1755328370 19417Installation Feet2-U Shaped notched holes(Foundfation

Page 44 - Made in Japan

8WIRING DIAGRAM5PUHZ-W90VHATB1MCMF121S463HTH3TH4TH6TH7TH8LEV-A, LEV-BDCLTerminal Block<Power Supply>TB2 Terminal Block<Controller>TB3 Term

Page 45 -  

9WIRING SPECIFICATIONS6FIELD ELECTRICAL WIRING (power wiring specifications)Outdoor unit power supply ~/N (single), 50Hz, 230 VOutdoor unit Circuit Br