Mitsubishi Q64AD User Manual Page 54

  • Download
  • Add to my manuals
  • Print
  • Page
    / 164
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 53
4 - 8 4 - 8
MELSEC-Q
4 SETUP AND PROCEDURES BEFORE OPERATION
4.5 Switch Setting for Intelligent Function Module
The settings for the intelligent function module are performed using the I/O assignment
settings for GX Developer.
(1) Setting item
The intelligent function module switches consist of switches 1 to 5 and are set
using 16 bit data. When the intelligent function module switches are not set, the
default value for switches 1 to 5 is 0.
Table 4.1 Switch setting item
Setting item
Analog input range Input range setting value
4 to 20 mA
0
H
1
0 to 20 mA 1
H
Switch 1
Input range setting
H
CH4CH3CH2CH1
1 to 5 V 2
H
0 to 5 V 3
H
– 10 to 10 V 4
H
0 to 10 V 5
H
User range setting F
H
Switch 2
Input range setting
H
CH8CH7CH6CH5
Switch 3 Not used
Switch 4
H
00
H
01 to FF
H
(numeric
value other than 00
H
)*
0
H
1 to F
H
(numeric
value other than 0
H
)*
0
H
1 to F
H
(numeric
value other than 0
H
)*
: With temperature drift correction
: Without temperature drift correction
: Normal resolution mode
: High resolution mode
: Normal mode (A/D conversion processing)
: Offset/gain setting mode
Switch 5 0 : Fixed
Setting any value within the setting range will provide the same operation.
When the setting range is 1 to F
H
, set 1 for example.
Depending on the type of module used, the settings for A/D unit input range are shown
below.
• Q64AD
· · · · ·
·
0
H
to 5
H
, F
H
• Q68ADV · · · · ·0
H,
2
H
to 5
H
, F
H
1 When the setting is 0
H
, the input operating range will be 0 t o 10 V.
• Q68ADI · · · · · ·0
H,
1
H
, F
H
Page view 53
1 2 ... 49 50 51 52 53 54 55 56 57 58 59 ... 163 164

Comments to this Manuals

No comments