MUCM Mitsubishi UPS Application ManualMUCM Modbus/MitsubishiUPSInstallation and Programming ManualThis Manual describes the MUCM application for inter
10 Installation 2 MUCM Mitsubishi UPS Application ManualLoading the Applications into the MUCMNOTE: If the MUCM were ordered with the part numbe
MUCM Mitsubishi UPS Application Manual 2 Installation 11QLOAD MUCM_MITSU_APP1Figure 2-6 QLOAD of MUCM_MITSU_APP11 Application Switch 1 (left)
12 Installation 2 MUCM Mitsubishi UPS Application ManualTable 2-1 MUCM Port Default SettingsThe MUCM will answer Modbus RTU requests on its RS-48
MUCM Mitsubishi UPS Application Manual 2 Installation 13Figure 2-7 Hyperterminal Setup Main Screen
MUCM Mitsubishi UPS Application Manual 3 Modbus Operation 153Modbus OperationThe Mitsubishi MUCM application uses Port 2 for Modbus communicat
16 Modbus Operation 3 MUCM Mitsubishi UPS Application Manual2033C Register ListThe data from the UPS is presented as Holding Registers (4x). Reg
MUCM Mitsubishi UPS Application Manual 3 Modbus Operation 17Table 3-4 2033C Register List (Output)Register Measurement Notes4x0032 Output Sour
18 Modbus Operation 3 MUCM Mitsubishi UPS Application ManualThe Alarms are mapped as bits in registers. If the alarm is active then its bit will
MUCM Mitsubishi UPS Application Manual 3 Modbus Operation 19Table 3-6 2033C Register List (UPS Setup)Register R/W Measurement Notes4x0499 R Re
Modbus and Momentum are registered trademarks of Modicon, Inc.Brand and product names mentioned in this document are trademarks or registeredtrademark
20 Modbus Operation 3 MUCM Mitsubishi UPS Application ManualTable 3-7 2033C Register List (UPS Setup)The MUCM serial port setup is stored in regi
MUCM Mitsubishi UPS Application Manual 3 Modbus Operation 21Table 3-8 MUCM Setup Register List2033D, 7011A, and 9800AD Register ListThe data f
22 Modbus Operation 3 MUCM Mitsubishi UPS Application ManualTable 3-9 2033D, 7011A, 9800AD Register List (Battery)Table 3-10 2033D, 7011A, 9800A
MUCM Mitsubishi UPS Application Manual 3 Modbus Operation 23Table 3-12 2033D, 7011A, 9800AD Register List (BYPASS)The Alarms are mapped as bi
24 Modbus Operation 3 MUCM Mitsubishi UPS Application ManualTable 3-14 2033D, 7011A, 9800AD Register List (UPS Setup)Register R/W Measurement N
MUCM Mitsubishi UPS Application Manual 3 Modbus Operation 25Table 3-15 2033D, 7011A, 9800AD Register List (UPS Setup)The MUCM serial port se
26 Modbus Operation 3 MUCM Mitsubishi UPS Application ManualTable 3-16 MUCM Setup Register List2033A and 9700 Register ListThe data from the UPS
MUCM Mitsubishi UPS Application Manual 3 Modbus Operation 27Table 3-17 2033A, 9700 Register List (Battery)Table 3-18 2033A, 9700 Register Lis
28 Modbus Operation 3 MUCM Mitsubishi UPS Application ManualTable 3-20 2033A, 9700 Register List (BYPASS)The Alarms are mapped as bits in regist
MUCM Mitsubishi UPS Application Manual 3 Modbus Operation 29Table 3-21 2033A, 9700 Register List (Alarms)Register Bit Code Description1 UF007
3Contents1 Introduction ...52 I
30 Modbus Operation 3 MUCM Mitsubishi UPS Application ManualTable 3-22 2033A, 9700 Register List (Alarms)Register Bit Code Description0 UF053 In
MUCM Mitsubishi UPS Application Manual 3 Modbus Operation 31Table 3-23 2033A, 9700 Register List (Alarms)Register Bit Code Description0 UF056
32 Modbus Operation 3 MUCM Mitsubishi UPS Application ManualTable 3-24 2033A, 9700 Register List (Alarms and Status)Register Bit Code Descriptio
MUCM Mitsubishi UPS Application Manual 3 Modbus Operation 33Table 3-25 2033A, 9700 Register List (Status)The MUCM serial port setup is stored
34 Modbus Operation 3 MUCM Mitsubishi UPS Application ManualTable 3-26 MUCM Setup Register ListRegister R/W Measurement Notes4x0653-4x0668RW MUCM
MUCM Mitsubishi UPS Application Manual 4 Examples 354ExamplesExample 1Figure 4-1 shows system with three UPSs to be connected to a Modbus mas
36 Examples 4 MUCM Mitsubishi UPS Application ManualFigure 4-1 Example 1 LayoutPort 2 of the MUCM is RS-485 so a simple 4-wire cable is required
MUCM Mitsubishi UPS Application Manual 4 Examples 37Figure 4-3 2-wire RS-485 ExampleMaster MUCM 1 MUCM 2 MUCM 3+ IN+ IN+ IN+- IN- IN- IN-OUT+
MUCM Mitsubishi UPS Application Manual 5 Testing and Troubleshooting 395Testing and TroubleshootingFigure 5-1 MUCM Lights and SwitchesSwitches
4Figure 2-2 MUCM to 25-pin UPS RS-232 (MU17 Cable) ...9Figure 2-3 MUCM to 4-wire Modbus Slav
40 Testing and Troubleshooting 5 MUCM Mitsubishi UPS Application Manual— Halt - The right position of this switch halts the application. Move to
MUCM Mitsubishi UPS Application Manual 5 Testing and Troubleshooting 41• Light 4 is a red light controlled by the application. Light 4 indica
42 Testing and Troubleshooting 5 MUCM Mitsubishi UPS Application Manual3 From the command line enter the following:>zapreg32 com1:9600,e,8,1 2
MUCM Mitsubishi UPS Application Manual 1 Introduction 51IntroductionThe Niobrara MUCM is a Modicon Momentum® compatible module that is capabl
MUCM Mitsubishi UPS Application Manual 2 Installation 72InstallationInstallation of the MUCM should go quickly, with the necessary materials.
8 Installation 2 MUCM Mitsubishi UPS Application ManualSoftware InstallationThe application files for the MUCM are included in theMUCM_MITSU_SETU
MUCM Mitsubishi UPS Application Manual 2 Installation 9Figure 2-2 MUCM to 25-pin UPS RS-232 (MU17 Cable)Port 2 to Modbus NetworkPort 2 of th