5. REMOVING THE NOZZLE ASSEMBLY AND DRAIN HOSE
(1) Remove the front panel (Refer to procedure 2).
(2) Remove the electrical box cover. (See Photo 2)
(3) Disconnect the connector (CN5V) on the indoor controller
board.
(4) After unhook the right side of the corner box, press the
upper left side and remove the corner box.
(5) Remove the nozzle assembly from the fixture.
(See Photo 5)
(6) Remove the drain hose.
Photo 5
Heat exchanger
Electrical box
Fixture
Drain hose
6. REMOVING THE LINE FLOW FAN AND THE FAN MOTOR
(1) Remove the front panel. (Refer to procedure 2)
(2) Remove the nozzle assembly. (Refer to procedure 5)
(3) Remove the electrical parts box. (Refer to procedure 4)
(4) Remove the fixture while pressing the right side of motor
fixture catch. (See Photo 6)
(5) Remove the left side of the motor fixture.
(6) Loosen the screw which fixes the line flow fan to the fan
motor, then remove the fan motor by sliding it to the right
side. (See Photo 6)
(7) Pull the left-hand side of the heat exchanger toward you.
(See Photo 7)
(8) Remove the line flow fan.
Photo 6
Heat exchanger
Fan motor
Photo 7
Heat exchanger
7. REMOVING THE VANE MOTOR
(1) Remove the front panel. (Refer to procedure 2)
(2) Remove the screw of the electrical parts box cover, and
remove the cover.
(3) Remove the 2 screws of the vane motor. (See Photo 8)
Disconnect the relay connector and remove the motor
from the shaft.
(4) Disconnect the vane motor connector (CN5V) on the
indoor controller board.
Photo 8
Heat exchanger
Vane motor
Nozzle assembly
8. REMOVING THE LIQUID PIPE THERMISTOR AND GAS
PIPE THERMISTOR
(1) Remove the front panel. (Refer to procedure 2)
(2) Remove the electrical box cover. (See Photo 2)
(3) Remove the water cut. (See Photo 3)
(4) Cut the wiring fixed band.
(5) Remove the liquid pipe thermistor and gas pipe thermistor.
(See Photo 9)
(6) Disconnect the connector (CN29) (CN21) on the indoor
controller board.
Photo 9
Heat exchanger
Drain hose
Fixture set screws
Set screws
Drain hose
Nozzle assembly
Fixture (left)
Nozzle assembly
Fixture
Line flow fan
Heat exchanger
fixture (left)
Vane motor fixing
screws
Gas pipe
thermistor
Liquid pipe thermistor
Electrical box
Fixture (right)