FX
2N
-4AD-TC SPECIAL FUNCTION BLOCK
USER’S GUIDE
JY992D65501F
This manual contains text, diagrams and explanations which will guide the reader in the correct installation
and operation of the FX
2N
-4AD-TC special function block and should be read and understood before
attempting to install or use the unit.
Further information can be found in the main unit manual and programming manual.
Guidelines for the Safety of the User and Protection of the FX
2N
-4AD-TC
special function block.
This manual should be used by trained and competent personnel. The definition of such a person or
persons is as follows:
a) Any engineer using the product associated with this manual, should be of a competent nature,
trained and qualified to the local and national standards. These engineers should be fully aware of
all aspects of safety with regards to automated equipment.
b) Any commissioning or service engineer must be of a competent nature, trained and qualified to
the local and national standards.
c) All operators of the completed equipment should be trained to use this product in a safe and
coordinated manner in compliance to established safety practices.
Note:
The term ‘completed equipment’ refers to a third party constructed device which contains or uses
the product associated with this manual.
Notes on the Symbols Used in this Manual
At various times throughout this manual certain symbols will be used to highlight points of information
which are intended to ensure the users personal safety and protect the integrity of equipment.
1) Indicates that the identified danger
WILL
cause physical and property damage.
2) Indicates that the identified danger could
POSSIBLY
cause physical and property
damage.
Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage
that may arise as a result of the installation or use of this equipment.
All examples and diagrams shown in this manual are intended only as an aid to understanding the
text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for the actual use of
the product based on these illustrative examples.
Owing to the very great variety in possible applications for this equipment, you must satisfy yourself as
to its suitability for your own specific application.
1. INTRODUCTION
The FX
2N
-4AD-TC analog block amplifies the signal from four thermocouple sensors (Type K or J) and
converts the data into 16 bit reading’s stored in the main unit. Both Centigrade (
°
C) and Fahrenheit
(
°
F) can be read.
Reading resolution is 0.4
°
C/0.72
°
F of Type K and 0.3
°
C/0.54
°
F of Type J.
The FX
2N
-4AD-TC can connected to the FX
0N
/FX
1N
/FX
3G
/FX
2N
/FX
3U
/FX
2NC
/FX
3UC
series
Programmable Controllers (PLC).
All data transfers and parameter settings are adjusted via software control of the FX
2N
-4AD-TC; by
use of the TO/FROM applied instructions in the PLC.
The FX
2N
-4AD-TC occupies 8 I/O points on the PLC expansion bus. The 8 I/O points can be allocated
from either inputs or outputs. The FX
2N
-4AD-TC draws 30mA from the 5V rail of the main unit or
powered extension unit.
Thermocouples with the following specifications can be used: Type K (JIS C 1602-1995)
Type J (JIS C 1602-1995)
2. EXTERNAL DIMENSIONS
3. CONNECTION WITH PLC
The FX
2N
-4AD-TC unit can be connected to the FX
0N
/FX
1N
/FX
3G
/FX
2N
/FX
3U
/FX
2NC
/FX
3UC
PLCs. Other
special units of blocks that use FROM/TO commands, such as analog input blocks, analog output blocks
and high-speed counter blocks, can be directly connected to the main unit of the PLC or to the right side of
other extension blocks or units. For the connection with PLCs, refer to the respective PLC manual.
4. WIRING
4.1 Wiring
*1:The compensating cables that can be used for
connecting with the thermocouple are the following.
Type K: KX-G, KX-GS, KX-H, KX-HS,WX-G,WX-H,VX-G
Type J: JX-G, JX-H
For every 10
of line resistance, the compensating
cable will indicate a temperature 0.12
°
C higher than
actual.
Check the line resistance before using.
Long compensating cables are more prone to noise
interference, therefore a short (less than 100m)
compensating cable is recommended.
Unused channels should have a wire link connected
between the + and - terminals to prevent an errors being
detected on that channel.
*2:If there is excessive electrical noise, connect the SLD
terminal to the ground terminal on the unit.
*3: Connect the ground terminals of the FX
2N
-4AD-TC unit and the main unit. Use grounding on the main
unit.
*4: The 24V DC built-in supply of the PLC may be used as the power supply.
4.2 Using crimp terminations
Use crimp terminals as indicated on the left.
The tightening torque must be 0.5 and 0.8 N
m. Do not tighten
terminal screws exceeding the specified torque. Failure to do so may
cause equipment failures or malfunctions.
Wire only to the module terminals discussed in this manual. Leave all
others vacant.
5. SPECIFICATIONS
5.1 General specification
5.2 Power supply specification
Item Specification
General specifications Same as those for the main unit
Dielectric withstand voltage 500V AC, 1min (between all terminals and ground)
Item Specification
Analog circuits 24V DC ± 10%, 50mA
Digital circuits 5V DC, 30mA (internal power supply from the main unit)
P O W E R
2 4 V
A / D
C H 4C H 3
C H 1
2 4 +
2 4 -
L +
L +
F X
2 N
- 4 A D - T C
L - L -
L +
L -
S L D
C H 1
2 4 +
2 4 -
L -
C H 2
L -
L +
L +
4 ( 0 . 1 6 )
4 ( 0 . 1 6 )
5 5 ( 2 . 1 7 )
8 0 ( 3 . 1 5 )
9 0 ( 3 . 5 4 )
5 5 ( 2 . 1 7 )
8 7 ( 3 . 4 3 )
9 ( 0 . 3 5 )
S L D
S L D
S L D
S L D
T e r m i n a l s c r e w s M 3 ( 0 . 1 2 )
2 4 V
L E D
A / D
L E D
D I N r a i l
m o u n t i n g s l o t
3 5 m m ( 1 . 3 8 )
M o u n t i n g h o l e s
4 . 5 m m ( 0 . 1 8 ) d i a .
E x t e n s i o n c a b l e
a n d c o n n e c t o r
Weight: Approx. 0.3 kg (0.66 lbs) Dimensions: mm (inches)
Accessories: Self adhesive labels for special function block number identification
Thermocouple
*1
shielded
CH1
3K
:
L+
24+
24-
DC/DC
converter
AG
+15V
-15V
PLC
Extension cable
D grounding
(100
:
or less)
*3
*4
24VDC±10% 50mA
*2
FX
2N
-4AD-TC
Analog Input Block
L-
CH1
SLD
Thermocouple
*1
shielded
CH4
L+
L-
SLD
3K
:
Temperature
compensation
circuit
CH4
l e s s t h a n
6 . 2 m m ( 0 . 2 4 )
U s e M 3 ( 0 . 1 2 )
l e s s t h a n
6 . 2 m m ( 0 . 2 4 )
5.3 Performance specification
Analog Inputs
Miscellaneous
Note: Earth-tipped thermocouples are not suitable for use with this unit.
5.4 Installation location
This unit measures temperature according to the temperature difference between the temperature
measurement part (themocouple) and the terminal block. If this unit is installed at a place where the
temperature of the terminal block varies rapidly, a measuring error may occur. For this reason, the unit
should be installed at a place free from excessive temperature variation.
6. ALLOCATION OF BUFFER MEMORIES (BFM)
6.1 Buffer memories
The FX
2N
-4AD-TC communicates
with the PLC via buffer memories.
BFMs #21 to #27 and #31 are
reserved.
All non reserved BFMs can be read
by the PLC using the FROM
instruction.
BFMs (buffer memories) marked
with an “*” can be written to, the
special function block using the TO
instruction.
Item
Centigrade (
°
C) Fahrenheit (
°
F)
Both
°
C and
°
F are available by reading the appropriate buffer memory (BFM).
Input signal
Thermocouple: Type K or J (either can be used for each channel), 4 channels, JIS
C 1602-1995
Rated temperature
range
Type K -100
°
C to +1,200
°
C Type K -148
°
F to +2,192
°
F
Type J -100
°
C to +600
°
C Type J -148
°
F to +1,112
°
F
Digital output
16-bit binary with sign
Type K -1,000 to +12,000 Type K -1480 to +21,920
Type J -1,000 to +6,000 Type J -1480 to +11,120
Resolution
Type K 0.4
°
CType K0.72
°
F
Type J 0.3
°
C Type J 0.54
°
F
Overall accuracy
Calibration point
± (0.5% full scale +1
°
C)
Freezing point of pure water 0
°
C / 32
°
F
Conversion speed (240ms ± 2%)
×
4 channels (unused channels are not converted)
Item Centigrade (
°
C) Fahrenheit (
°
F)
Conversion Characteristics
Readings given at calibration
reference point 0
°
C/32
°
F (0/320)
respectively.
(subject to the overall accuracy)
Item Specification
Isolation
Photo-coupler isolation between analog and digital circuits.
DC/DC converter isolation of power from main unit.
No isolation between analog channels.
Number of occupied I/O points
The block occupies 8 I/O points
(can be either inputs or outputs)
+6,000
-100°C
-1,000
+1,200°C
+12,000
(Type K)
(Type J)
+600°C
(Type K)(Type J)
-1,480
+2,192°F
+21,920
(Type K)
(Type J)
+1,112°F
(Type K)(Type J)
+11,120
-148°F
BFM CONTENTS
*#0
Thermocouple Type K or J selection mode.
At shipment: H0000
*# 1 - #4
CH1 to CH4 Averaged temperature reading to be
averaged (1 to 256) Default = 8
#5 - #8 CH1 to CH4 Averaged temperature in 0.1
°
C units
#9 - #12 CH1 to CH4 Present temperature in 0.1
°
C units
#13 - #16 CH1 to CH4 Averaged temperature in 0.1
°
F units
#17 - #20 CH1 to CH4 Present temperature in 0.1
°
F units
#21 - #27 Reserved
*#28 Digital range error latch
#29 Error status
#30 Identification code K2030
#31 Reserved
Page view 0
1 2 3 4 5 6 7 8

Summary of Contents

Page 1 - USER’S GUIDE

FX2N-4AD-TC SPECIAL FUNCTION BLOCKUSER’S GUIDEJY992D65501FThis manual contains text, diagrams and explanations which will guide the reader in the corr

Page 2

FX2N-4AD-TC SPECIAL FUNCTION BLOCKUSER’S GUIDEJY992D65501FThis manual contains text, diagrams and explanations which will guide the reader in the corr

Page 3

FX2N-4AD-TC SPECIAL FUNCTION BLOCKUSER’S GUIDEJY992D65501FThis manual contains text, diagrams and explanations which will guide the reader in the corr

Page 4 - 10.EMC CONSIDERATIONS

HEAD OFFICEHIMEJI WORKS : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN : 840, CHIYODA CHO, HIMEJI, JAPANThis manual confers no

Page 5

HEAD OFFICEHIMEJI WORKS : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN : 840, CHIYODA CHO, HIMEJI, JAPANThis manual confers no

Page 6

HEAD OFFICEHIMEJI WORKS : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN : 840, CHIYODA CHO, HIMEJI, JAPANThis manual confers no

Page 7

FX2N-4AD-TC SPECIAL FUNCTION BLOCKUSER’S GUIDEJY992D65501FThis manual contains text, diagrams and explanations which will guide the reader in the corr

Page 8

HEAD OFFICEHIMEJI WORKS : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN : 840, CHIYODA CHO, HIMEJI, JAPANThis manual confers no

Comments to this Manuals

No comments