1. Model Selection (With actual examples)
First step, to select the approximate model:
Based on the cooling load and the cooling capacity listed in the capacity table, select the applicable model.
Notes:
*1. The correct WB is required since it has a serious effect on the capacity.
*2. The cooling capacity decreases as the outdoor temperature increases. Therefore, the estimated highest
temperature during an air conditioning time frame is the designed outdoor temperature. However, it is
recommended that the abnormal outdoor temperature which may occur once or twice a year be excluded from
the calculation to avoid selection of an excessively large capacity model.
*3. The wind pressure loss of an air duct should be calculated correctly. If a value having an excessive allowance is
used, an excessively large model will be selected. Moreover, an excessively high air flow will be induced during
actual operation causing the generation of high operating sounds and carry-over of condensed water.
(Step-1) Confirmation of operation range
Confirm that the conditions given above for the model to be selected are within the operation
range listed on Page 18.
(Step-2) Calculation of actual air flow, external static pressure, and fan motor input
Based on the designed air flow and external static pressure, obtain the actual air flow and fan motor
power from the fan performance table for the model input selected. For an explanation of how to
use the fan performance table, see the following examples.
Example: PRHG-10, 50Hz
Example 1. (To operate with values near to the designed air flow and external static pressure.)
Condition : Designed air flow 100CMM
Designed external static pressure 60Pa
Calculation : The designed point is A. Therefore, duct
resistance line passing A is dotted line.
Therefore, actual point is B for
fan speed 1088rpm.
(Select a pulley near A point to fan speed.)
Actual air flow = 110CMM
Second step, to select the model:
To select the model, the following conditions must be known:
(1) Total cooling load or sensible cooling load
(2) Indoor conditioned temperature (WB*1, DB)
(3) Designed outdoor temperature (DB)*2
(4) Designed air flow
(5) Designed external static pressure (= Wind pressure loss of air duct)*3
internal static pressure
Air flow
1500
90 95 100 105
1670
(CMM)
(L/S)
1.5kw
2.2kw
900
1000
1100
1200
1300
1400
100
200
300
400
500
Total static pressure (Pa)
Fan speed
<rpm>
1500
110 115
1830
120
2000
600
700
800
1600
1700
SELECTION PROCEDURE
A
B
60Pa
-7-