How to check mis-wiring and serial signal error (when outdoor unit does not work)
• When unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch.
Indoor unit does not operate.
• When OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-second.
Outdoor unit does not operate.
Is serial signal
error indicated
6 minutes later?
No
· Turn OFF inverter-controlled lighting
equipment.
· Turn OFF the power supply and then
turn ON it again.
· Press EMERGENCY OPERATION
switch.
· Reinstall
either the
unit or the
light each
other away.
· Attach a filter
on receiving
section of
the indoor
unit.
Yes
B
A
Is there rated voltage of
230V AC in the power
supply?
Does the LED1 on the outdoor electronic
control P.C. board repeat quick blinking
"3.6-second-OFF and 0.8-second-ON"?
Is there any mis-
wiring, poor contact,
or wire disconnection
of the
indoor/outdoor
connecting wire?
W1. If short-circuiting with the indoor/outdoor unit connecting
wire kept connected, make sure the wire is correctly
connected,otherwise the board may be broken.
(Lighting
or
not lighting)
No
Yes
No
Yes
Yes
No
Yes
No
Yes
No
W2 Be careful to the residual
voltage of smoothing capacitor.
Be sure to release the failure-mode
recall function after checking.
No
No
Yes
No
Yes
Serial signal error display
Yes
As for indoor unit, refer to service manual OB371,OB378 and OB388.
Turn OFF the power supply.
Turn ON the power supply.
Is there 230V AC between
outdoor terminal block S1 and
S2?
Does the left lamp of OPERATION INDICATOR
lamp light up? <Confirmation of the power to
the indoor unit>
Press EMERGENCY OPERATION switch.
Check the power
supply.
Is the self-check of the indoor unit displayed 6
minutes after?
The left lamp of
OPERATION INDICATOR
lamp blinks quickly.
A
Turn OFF the power supply.
Check once more if the indoor/outdoor
connecting wire is not mis-wiring.
Short-circuit outdoor terminal block S2 and
S3.(The indoor/outdoor connecting
wire can be kept connected.) W1
B
Turn ON the power supply of the outdoor unit.
Check the wiring.
Make them sure.
Remove the short-circuit between
outdoor terminal block S2 and S3.
Is there amplitude of 10 to 20V DC
between outdoor terminal block S2
and S3?
Replace the indoor electronic control P.C. board.
Replace the outdoor electronic
control P.C. board.
W2
Is there any error of the
indoor/outdoor connecting wire,
such as the damage of the wire,
intermediate connection, poor
contact to the terminal block?
Replace the
indoor/outdoor
connecting.
Outdoor electronic control P.C. board
Blinking
(Parts side)
LED2
LED1
OB389 --2qxp 05.1.26 18:15 Page 35