Mitsubishi MXZ-4A80VA Installation Manual

Browse online or download Installation Manual for Split-system air conditioners Mitsubishi MXZ-4A80VA. Mitsubishi MXZ-4A80VA Installation manual User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 12
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Refer to the installation manual of each indoor unit for indoor unit installation.
INSTALLATION MANUAL
FOR INSTALLER
CONTENTS
1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR
SAFETY ........................................................................................... 2
2. INSTALLATION DIAGRAM & ACCESSORIES ................................ 2
3. SELECTING THE INSTALLATION LOCATION ................................ 3
4. OUTDOOR UNIT INSTALLATION ................................................... 4
5. INDOOR/OUTDOOR UNITS CONNECTION FINISHING AND
TEST RUN ....................................................................................... 6
SPLIT-TYPE AIR CONDITIONER
Model MXZ-4A80VA
HFC
utilized
R410A
IMPORTANT NOTES
TO COMPLY WITH THE REQUIREMENTS OF AUSTRALIAN
STANDARD AS 3000 S.A.A. WIRING RULES, THE ELECTRICAL
WIRING REQUIRED BETWEEN THE INDOOR AND OUTDOOR
UNITS MUST BE INSTALLED BY A LICENCED ELECTRICAL CON-
TRACTOR.
Page view 0
1 2 3 4 5 6 ... 11 12

Summary of Contents

Page 1 - CONTENTS

Refer to the installation manual of each indoor unit for indoor unit installation.INSTALLATION MANUALFOR INSTALLERCONTENTS1. THE FOLLOWING SHOULD ALWA

Page 4 - 4-1 INSTALLING THE UNIT

HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPANSG79Y674H01

Page 5 - SUPPLY CORD CONNECTION

2KHFIJECD2. INSTALLATION DIAGRAM & ACCESSORIES1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FORSAFETY• Be sure to read “THE FOLLOWING SHOULD ALWAYS B

Page 6 - 5-1 FLARED CONNECTIONS

3Parts to be locally procuredAPower supply cord1(3-core 2.5 mm2)BIndoor/outdoor unit connecting wire1(4-core 1.0 mm2/1.5 mm2)CExtension pipe According

Page 7 - 5-3 PIPE CONNECTION

44. OUTDOOR UNIT INSTALLATION4-1 INSTALLING THE UNIT• Be sure to fix the unit’s legs with bolts when installing it.• Be sure to install the unit firml

Page 8 - DRY, HEAT)

5Connect to the supply terminals and leave a contact separation of at least 3 mm at each pole todisconnect the source power pole. (When the power swit

Page 9 - 5-10 TEST RUN

6CopperpipeGoodNo goodTilted UnevenBurredBurrCopper pipeSparereamerPipe cutterFlare nutCopper pipe5-2 FLARING WORK• Main cause of gas leakage is defec

Page 10

7ADieCopper pipeFlare nutDieCopper pipeSmooth all aroundEven lengthall aroundInside is shining without any scratchesYork4. Flaring work• Perform flari

Page 11

8 WARNING:When installing or moving the unit, do not mix anything other than specified refrigerant (R410A) intothe refrigerating cycle.If air is mixed

Page 12 - SG79Y674H01

9ABCD5-9 GAS CHARGEPerform gas charge to unit.1 Connect gas cylinder to the service port of stop valve.2 Perform air purge of the pipe (or hose) comin

Comments to this Manuals

No comments