- 9 -* Main and sub system controllers (M-NET)AG-150A is for exclusive use as a main SC. AG-150A cannot be used as a sub SC.• Main system controller (
- 10 -1. Field-supplied Parts1Electric box: PAC-YG83UTB (sold separately) (When following installation method described in section “2. Installation” i
- 11 -2-1. Embedding the centralized controller in the wall.1 Ensure there is enough space to install the controller as shown in the figure at right.2
- 12 -4 Attach the A type installation plate (supplied) to the B type installation plate (supplied) with the M4 flathead screws (supplied), sandwichin
- 13 -7 Attach the controller to the A type installation plate with the M4 roundhead screws (supplied).8 Replace the AG-150A surface cover.2-2. Wall-E
- 14 -4 Cut out an opening in the wall as shown in the shaded area in the figure below. (Width × Height: 278 mm (11 in) × 152 mm (6 in)) Follow the di
- 15 -9 Attach the controller to the A type installation plate with the roundhead screws (supplied).0 Replace the AG-150A surface cover.2-3. Wall-moun
- 16 -2 Punch out the appropriate knockout hole, depending on how the wiring is routed.3 Sand the cut surface of the knockout hole smooth.4 Push the M
- 17 -2-4. Installing the centralized controller and a power supply unit (PAC-SC51KUA; sold separately) inside the mounting attachment A type (PAC-YG8
- 18 -0 Connect the wiring from the power supply unit to the centralized controller.a Install the controller inside the mounting attachment A type (PA
- 1 -This manual describes how to install the centralized controller and wiring. Before installing the controller, read the 1 Safety Precautions s
- 19 -2-5. Installing the centralized controller on the control board1 Make sure that there is an adequate amount of space to install the controller a
- 20 -7 Screw down the A type installation plate (supplied) on the control board door with the M4 flathead screws (supplied). Drill four screw holes a
- 21 -1. System without connection to a PAC-YG50ECA Expansion controller7 WiringNOTESConnecting the M-NET transmission line to the AG-150A.* Connect t
- 22 -2. System with connection to a PAC-YG50ECA Expansion controllerNOTESConnecting the PAC-YG50ECA Expansion controller (sold separately)* Supply 24
- 23 -System 1: Standard configuration (system with 50 units of equipments or less)System 2: System with connection to one or more Expansion controlle
- 24 -• Before performing a test run, verify that the group setting has been performed and the startup sequence for the interlocked operation setting
- 25 -1. System with connection to a PAC-YG50ECA Expansion controller2. Using multiple system controllers• Make the initial settings (e.g., group sett
- 26 -1. External signal input function* External signal input requires the external I/O adapter (PAC-YG10HA) sold separately.(1) External inputEmerge
- 27 -(4) Recommended circuit(A) For level signal(B) For pulse signal1 The contact relay, DC power source, extension cable, etc., must be prepared on
- 28 -When using the LAN connection function, insert the LAN cable to the LAN connector of the controller.* Connect the LAN cable from the AG-150A to
- 2 -* The Installation Manual and the parts listed below are included with the unit.*1 ISO metric screw thread*2 If the enclosed screw for attaching
- 29 -13 Optional AccessoriesParts Model Usage NotePower supply unit PAC-SC51KUASupplies power to the controller and M-NET transmission line.Expansion
WT05368X08.fm Page 30 Thursday, March 17, 2011 9:21 AM
WT05368X08 Printed in JapanThis product is designed and intended for use in the residential, commercial and light-industrial environment.The produc
- 3 -3 External DimensionsUnit: mm (in)250 (9-7/8)272 (10-3/4)146 (5-3/4)167 (6-5/8)Back View290.8 (11-1/2)273 (10-3/4)250 (9-7/8)200 (7-7/8)147 (5-13
- 4 -AG-150A is a centralized controller that features advanced functions such as the Web function.Air conditioning units connected to this controller
- 5 -NOTE* M-NET terminal (A, B, S) and CN1 cannot be used simultaneously.* Power supply terminal block (V+, V-, FG) and CN2 cannot be used simultaneo
- 6 -1. Standard configuration (using the AG-150A to control a system with 50 or fewer units of equipments)* Address setting for each M-NET device (Ad
- 7 -1-1. M-NET wiring configuration(1) Types and maximum allowable length of M-NET transmission cablesThe wiring diagram below shows a sample M-NET t
- 8 -2. System with connection to an Expansion controller (system with 51 or more units)• Refer to the PAC-YG50ECA Expansion controller Installation/I