30 31
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
*
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : The values are for one indoor unit operation.
*
3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
SPECIFICATIONS The values are for simultaneous Multi operation.
SPECIFICATIONS
The values are for simultaneous Multi operation.
SPECIFICATIONS
The values are for simultaneous Multi operation.
FDT
FDT 40/50/60/71/100/125
CEILING CASSETTE
-4way-
RC-E5RC-EX1A
Wired
RCH-E3
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
*
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : The values are for one indoor unit operation.
*
3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
RCN-T-36W-E
Wireless
Powerful-Hi can be selected. Sound level: 200VSPVF1 51dB, 250VSPVF 51dB, 140VSTVF 39dB, 200VSTVF1 46dB, 200VSDVF 39dB, 250VSDVF 46dB
Air flow: 200VSPVF1 37m
3
/min, 250VSPVF 37m
3
/min, 140VSTVF 20m
3
/min, 200VSTVF1 28m
3
/min, 200VSDVF 20m
3
/min, 250VSDVF 28m
3
/min
Powerful-Hi can be selected. Sound level: 100VN(S)PVF 39dB, 125VN(S)PVF 46dB, 140VN(S)PVF1 46dB, 140VNTVF 39dB
Air flow: 100VN(S)PVF 20m
3
/min, 125VN(S)PVF 28m
3
/min, 140VN(S)PVF1 28m
3
/min, 140VNTVF 20m
3
/min
SPECIFICATIONS
The values are for simultaneous Multi operation.
R410A
Powerful-Hi can be selected. Sound level: 71VNXPVF 39dB, 100VN(S)XPVF 39dB, 125VN(S)XPVF 46dB, 140VN(S)XPVF1 46dB, 140VN(S)XTVF 39dB
Air flow: 71VNXPVF 20m
3
/min, 100VN(S)XPVF 20m
3
/min, 125VN(S)XPVF 28m
3
/min, 140VN(S)XPVF1 28m
3
/min, 140VN(S)XTVF 20m
3
/min
MULTI [ INDOOR UNIT ]
Remote control (Option)
Set model name
FDT71VNXPVF FDT100VNXPVF
Twin
Indoor unit FDT40VF FDT50VF
Outdoor unit FDC71VNX FDC100VNX
Power source
1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz
Nominal cooling capacity (Min~Max) kW 7.1 ( 3.2 ~ 8.0 ) 10.0 ( 4.0 ~ 11.2 )
Nominal heating capacity (Min~Max) kW 8.0 ( 3.6 ~ 9.0 ) 11.2 ( 4.0 ~ 12.5 )
Power consumption Cooling/Heating kW 1.85 / 1.99 2.56 / 2.66
EER/COP Cooling/Heating 3.84 / 4.02 3.91 / 4.21
Inrush current 220/230/240 V
A
5 5
Max. running current 17 24
Sound power
level*
1
Indoor*
2
Cooling/Heating
dB(A)
55 / 55 55 / 55
Outdoor
Cooling/Heating 66 / 66 70 / 70
Sound
pressure
level*
1
Indoor*
2
Cooling (Hi/Me/Lo)
33 / 31 / 30 33 / 31 / 30
Heating (Hi/Me/Lo)
33 / 31 / 30 33 / 31 / 30
Outdoor
Cooling/Heating 51 / 48 48 / 50
Air flow
Indoor*
2
Cooling (Hi/Me/Lo)
m
3
/min
18 / 16 / 14 18 / 16 / 14
Heating (Hi/Me/Lo)
18 / 16 / 14 18 / 16 / 14
Outdoor
Cooling/Heating 60 / 50 100 / 100
Exterior
dimensions
Indoor
HeightxWidthxDepth
mm
Unit: 246 x 840 x 840 Panel: 35 x 950 x 950
Outdoor
750 x 880(+88) x 340
1,300 x 970 x 370
Net weight
Indoor
kg
27.5(Unit:22 Panel:5.5)
Outdoor
60 105
Ref.piping size
Liquid/Gas ømm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max. 50 Max. 100
Vertical height differences
Outdoor is higher/lower
m Max.30 / Max.15
Outdoor operating
temperature range
Cooling
°C
-15~43*
3
Heating -20~20
Panel T-PSA-3BW-E
Air filter, Q'ty Pocket plastic net X 1(Washable)
Remote control (option)
wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-T-36W-E
Set model name
FDT125VNXPVF FDT140VNXPVF1 FDT140VNXTVF FDT100VSXPVF FDT125VSXPVF FDT140VSXPVF1 FDT140VSXTVF
Twin Triple Twin Triple
Indoor unit FDT60VF FDT71VF1 FDT50VF FDT50VF FDT60VF FDT71VF1 FDT50VF
Outdoor unit FDC125VNX FDC140VNX FDC140VNX FDC100VSX FDC125VSX FDC140VSX FDC140VSX
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz 3 Phase 380-415V 50Hz, 3 Phase 380V 60Hz
Nominal cooling capacity (Min~Max) kW 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 ) 14.0 ( 5.0 ~ 16.0 ) 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 16.0 ) 14.0 ( 5.0 ~ 16.0 )
Nominal heating capacity (Min~Max) kW 14.0 ( 4.0 ~ 17.0 ) 16.0 ( 4.0 ~ 18.0 ) 16.0 ( 4.0 ~ 18.0 ) 11.2 ( 4.0 ~ 16.0 ) 14.0 ( 4.0 ~ 18.0 ) 16.0 ( 4.0 ~ 20.0 ) 16.0 ( 4.0 ~ 20.0 )
Power consumption Cooling/Heating kW 3.06 / 3.22 3.88 / 3.70 3.88 / 3.76 2.56 / 2.66 3.06 / 3.22 3.88 / 3.70 3.88 / 3.76
EER/COP Cooling/Heating 4.08 / 4.35 3.61 / 4.32 3.61 / 4.26 3.91 / 4.21 4.08 / 4.35 3.61 / 4.32 3.61 / 4.26
Inrush current 220/230/240 V
A
5 5 5 5 5 5 5
Max. running current 26 26 26 15 15 15 15
Sound power
level*
1
Indoor*
2
Cooling/Heating
dB(A)
60 / 60 64 / 64 55 / 55 55 / 55 60 / 60 64 / 64 55 / 55
Outdoor
Cooling/Heating 70 / 70 72 / 72 72 / 72 70 / 70 70 / 70 72 / 72 72 / 72
Sound
pressure
level*
1
Indoor*
2
Cooling (Hi/Me/Lo)
33 / 31 / 30 35 / 33 / 31 33 / 31 / 30 33 / 31 / 30 33 / 31 / 30 35 / 33 / 31 33 / 31 / 30
Heating (Hi/Me/Lo)
33 / 31 / 30 35 / 33 / 31 33 / 31 / 30 33 / 31 / 30 33 / 31 / 30 35 / 33 / 31 33 / 31 / 30
Outdoor
Cooling/Heating 48 / 50 49 / 52 49 / 52 48 / 50 48 / 50 49 / 52 49 / 52
Air flow
Indoor*
2
Cooling (Hi/Me/Lo)
m
3
/min
18 / 16 / 14 21 / 19 / 17 18 / 16 / 14 18 / 16 / 14 18 / 16 / 14 21 / 19 / 17 18 / 16 / 14
Heating (Hi/Me/Lo)
18 / 16 / 14 21 / 19 / 17 18 / 16 / 14 18 / 16 / 14 18 / 16 / 14 21 / 19 / 17 18 / 16 / 14
Outdoor
Cooling/Heating 100 / 100 100 / 100 100 / 100 100 / 100 100 / 100 100 / 100 100 / 100
Exterior
dimensions
Indoor
HeightxWidthxDepth
mm
Unit: 246 x 840 x 840 Panel: 35 x 950 x 950
Outdoor
1,300 x 970 x 370
Net weight
Indoor
kg
29.5(Unit:24 Panel:5.5) 27.5(Unit:22 Panel:5.5) 29.5(Unit:24 Panel:5.5)
27.5(Unit:22 Panel:5.5)
Outdoor
105
Ref.piping size
Liquid/Gas ømm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.100
Vertical height differences
Outdoor is higher/lower
m Max.30 / Max.15
Outdoor operating
temperature range
Cooling
°C
-15~43*
3
Heating -20~20
Panel T-PSA-3BW-E
Air filter, Q'ty Pocket plastic net x 1(Washable)
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-T-36W-E