10-3. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed
are memorized by the indoor electronic control P.C.board. The “AUTO RESTART FUNCTION” sets to work the moment
power has restored after power failure. Then, the unit will restart automatically. However if the unit is operated in “I FEEL
CONTROL.” mode before power failure, the operation is not memorized. In “I FEEL CONTROL.” mode, the operation is
decided by the initial room temperature.
How to set “AUTO RESTART FUNCTION”
1Turn off the main power for the unit.
2Remove the electronic control P.C. board and the display P.C.board. (Refer to page 61 or 63.)
3Cut the RESISTOR JR06(MS-18/24RV)/ JR07(MS-30RV) on the indoor electronic control P.C.board. (Refer to page 58
or 59.)
JR06
CN102
CN151
CN112 CN111 CN121
CN101
BZ
SW
52C
IC101 RA102
IC141
CN211
C11CN201
JR07
IC152
CN151
CN112
CN111
CN121
SW1
IC101
RA102
C11
CN201
CN211
TAB12
Operation
1If the main power (220-240V AC) has been cut, the operation settings remain.
2After the power is restored, the unit restarts automatically according to the memory.(However, it takes at least 3 minutes
for the compressor to start running.)
NOTE:
The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote
controller.
If main power is turned off or a power failure occurs while AUTO START/STOP timer is active, the timer setting is
cancelled.
If the unit has been off with the remote controller before power failure, the auto restart function does not work as the
power button of the remote controller is off.
To prevent breaker off due to the rush of starting current, systematize other home appliances not to turn on at the same
time.
When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart.
Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current
by adding to the system that allows the units to start one by one.
MS-18/24RV MS-30RV
OB271--2.qxp 2/7/01 9:04 AM Page 46