Mitsubishi MS-18RV Service Manual Page 57

  • Download
  • Add to my manuals
  • Print
  • Page
    / 76
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 56
57
Check of outdoor thermistor
Measure
resistance
between CN 662
3 and 4.
No
Yes
Replace the
thermistor.
Measure
resistance
between CN 662
1 and 2.
Connect CN662.
Turn ON the power
supply and press
the EMERGENCY
OPERATION
switch.
Does the resistance
of thermistor have the
characteristics on
page 60?
No
Yes
Does the unit operate
10 minutes or more?
Replace the deicer P.C.
board.
Ok W1.
W1. It is thought defective contact of the connector.
Turn OFF the
power supply.
Discharge temperature
thermistor(RT62)
Ambient temperature
thermistor(RT63)
Thermistors in the outdoor unit are abnormal.
w Disconnect the connectors CN662 from the deicer P.C. board. (Check the characteristics of each thermistor.)
H
Check of LEV (Expansion valve)
G
With remote controller set toward the indoor unit, press
OPERATE/ STOP(ON/ OFF) button and confirm one
beep tone.
LEV operates in full-opening
direction.
Is LEV coil properly fixed to
the body?
Cooling does not operate.
Ok
Do you hear LEV "click,
click·······"?
Do you touch LEV and feel
it vibrate?
Does the resistance of thermistor
have the characteristics?
No
Yes
Yes
Yes
No
LEV (CN724)
WHT–RED
RED–ORN
YLW–BRN
BRN–BLU
Resistance
30.3 " ~ 37.0 "
Characteristics of LEV coil
No
Properly fix LEV coil to
the body.
Replace the
DEICER P.C. board.
NOTE : After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply of the unit and turn ON again.
2. Press the RESET button on the remote controller.
Replace the
LEV coil.
1 During pressing OPERATION SELECT button
on remote controller, press RESET button.
2 First, release RESET button.
(Confirm all displays of remote controller.)
3 Then release OPERATION SELECT button.
1 During pressing OPERATION SELECT
button on remote controller, press
RESET button.
2 First, release RESET button.
(Confirm all displays of remote controller.)
3 Then release OPERATION SELECT button.
AMPM
CLOCK
˚C
AMPM
<MS-30RV only>
<MS-30RV only>
OB271--2.qxp 2/7/01 9:04 AM Page 57
Page view 56
1 2 ... 52 53 54 55 56 57 58 59 60 61 62 ... 75 76

Comments to this Manuals

No comments