Function Settings
The timeout for turning OFF the backlight, validating or invalidating of the auto mode button and locking or
unlocking the individual functions of the remote controller are set.
When changing the Function Settings, follow the following steps.
1. Press the FUNCTION SETTING button on the MAIN MENU.
Page 7
[Function Setting screen]
2. Select the Backlight Timeout time using the ▲▼ buttons. (Factory default : 10)
Time from the last operation on the touch panel until the monitor backlight turns OFF can be selected.
3. Select the Brightness using the ▲▼ buttons. (Factory default : 7)
Brightness for the monitor backlight can be selected.
4. Press the "Valid" or "Invalid" button for the Auto Mode. (Factory default : Invalid)
This enables or disables the AUTO button on the GROUP SETTINGS screen and CHANGE All screen.
If you set Auto Mode to INVALID,
Auto button is not shown on the screen.
This function can be applied to the outdoor units, which are the cooling / heating free multi KXR, GHP-R
series or later and PAC.
For other than the outdoor units above, please do not use Auto Mode.
Please contact the shop where the unit was purchased.
5. Select the "Closed" or "Open" for the Malfunction Output (Normal). (Factory default : Closed)
You can choose "Closed" or "Open" status for malfunction output during normal operation of air conditioning unit.
Contact your service representative or installer for further information.
6. Press the "Valid" or "Invalid" button for the Individual Lock/Unlock. (Factory default : Invalid)
This enables or disables permitting and prohibiting the individual operation such as run/stop, mode and
temperature settings of the remote controller.
Note
This function can be applied to the indoor units, which are the model KXE4 or later, and to the remote
controller, which is the model RC-E1 or later.
7. Press the "Unlock" or "Lock" button for the Remote Controller's Timer. (Factory default : Unlock)
This permits or prohibits remote controller's timer operation for all the air conditioners defined in a group.
8. Press the Change button.
You can specify the folder to transfer the calculated data to USB memory. (SC-SL3N-BE only)
9. Use it when set the communication system (Factory default : New). Usually, this is not necessary to
change it.
If setting is incorrect, this may cause no communication with a part or all of air conditioners.
Please contact the shop where the unit was purchased.
10. In case that managing one air conditioner with plural center consoles, different setting is performed
to the same air conditioner, and this may cause that remote controller does not be operated according
to the intention. In such case, make this setting to "Invalid" other than the primary central control.
(Factory default :Valid)
In addition, make this setting to "valid" when the external input wiring such as emergency stop input are
connected to this central control.
Please contact the shop where the unit was purchased
11. Press the SET button.
Press the Cancel button to cancel the change.
Note
Set the timeout of the backlight as short as possible in order to make the lifetime of LCD longer.