AIR-COOLED SPLIT-TYPE DUCTED AIR CONDITIONERS
DATA BOOK
Series : PE(H)
Cooling only
Model Service ref.
PE-7MYC PE-7MYC-EU
PE-8MYC PE-8MYC-EU
PE-10MYC PE-10MYC-EU
PE-15MYC PE-15MYC-EU
PE-20MYC PE-20MYC-EU
Heat pump
PEH-5MYA PEH-5MYA-EU
PEH-7MYA PEH-7MYA-EU
PEH-8MYA PEH-8MYA-EU
PEH-10MYA PEH-10MYA-EU
PEH-15MYA PEH-15MYA-EU
PEH-20MYA PEH-20MYA-EU
Page view 0
1 2 3 4 5 6 ... 114 115

Summary of Contents

Page 1 - DATA BOOK

AIR-COOLED SPLIT-TYPE DUCTED AIR CONDITIONERS DATA BOOKSeries : PE(H)Cooling onlyModel Service ref.PE-7MYC PE-7MYC-EUPE-8MYC PE-8MYC-EUPE-10MYC PE-10M

Page 2 - CONTENTS

Model nameServicereferencePower supply IndoorOutdoorkWBtu/hkcal/h%Capacity stepRefrigerantRefrigerant charge kgCapillary tubeRefrigerant controlIndoor

Page 3 - SAFETY FOR USE

- 99 -Control module of outdoor unit PU(H)-7, 8, 10Control module of outdoor unit PU-15Upper blowPUH onlyPUH onlyPUH onlyTerminal block forconnectio

Page 4

- 100 -Method for connecting electric wirePlease do the wiring after consulting the electric powercompany of jurisdiction beforehand in the instructio

Page 5 - A COMPLETE LINE UP

- 101 -(3) Indoor unit and remote controller.(OPTION:PAC-204RC)TB4CZ1FZ24VAC(N)COMP1FAN HI23TB41F2(3.15A)GRAYGRAYTB3CZ1-1CZ1-2FZ24VAC(N)COMP1COMP2FAN

Page 6 - DESCRIPTIONS

8. Before starting the Trial run.Check itemsPerform trial operation after completion of the above items.(1) Check to see wheter there are refrigerant

Page 7 - MECHANICAL SPECIFICATIONS

- 103 -INSTRUCTIONS FOR USE1.Check points for operation.Check the following points before you operate your air conditioner.(1)Check that there is noth

Page 8 - PE-10 MYC

- 104 -2.Caution for use.Keep the following points in mind to safeguard against failures and breakdowns.(1) This air conditioner does not restart with

Page 9 - SPECIFICATIONS

- 105 - 3.3 Cleaning the Outdoor Unit Heat ExchangerIf you use your air conditioner for prolonged periods, the outdoor heat exchanger will becom

Page 10 - Heat pump

- 106 -6-2 Place for installation.Please do not use the unit in the following places.(1) Place where a lot of oil (The machine oil is contained), mois

Page 11 - PEH-10,15,20MYA

- 107 -7.Trouble shootingBefore you ask for repair service, check the following points:State of MachineCool or warm air does not come out.CauseAir flo

Page 12 - ELECTRICAL DATA

- 108 -HOW TO OPERATE (OPTION PAC-204RC)For purposes of explanation, all the displays on this page are shownin their lit condition. This configuration

Page 13 - PEH-5,7,8MYA-EU

Model nameServicereferencePower supply IndoorOutdoorkWBtu/hkcal/h%Capacity stepRefrigerantRefrigerant charge kgCapillary tubeRefrigerant controlIndoor

Page 14 - PEH-10,15,20MYA-EU

- 109 -1AOperation mode displayA1-2 Selecting operationWhen selecting operationPress the [MODE] buttonConsecutive press of the [MODE] button switches

Page 15 - SELECTION PROCEDURE

- 110 -1-4 Time setting124 Clock keyCurrent time displayPress the key one time will activate set clock mode. Press the key again will disable set cloc

Page 16 - 2. Efficiency Calculation

- 111 -1-6.Trouble shootingBefore you ask for repair service, check the following points:Error DisplayState of MachineCool air or warm air does not co

Page 17 - CAPACITY TABLES

- 112 -SPECIFICATION GUIDELINESDue to continuous product development, these guidelines are subject to change.Air to air reverse cycle split air condit

Page 19

HEAD OFFICE DENKI BLDG., MARUNOUCHI,TOKYO 100-0005,TELEX J24532 CABLE MELCO TOKYOMITSUBISHI ELECTRIC CORPORATIONIssuued in Dec. 1999 MEE99K014New publ

Page 20

- 11 -ELECTRICAL DATAVOLT ITEMTOTAL INPUT kWTOTAL RUN CURRENT APOWER FACTOR %START CURRENT APE-7240VPE-8 20415VCOMPRESSOR INPUT kW RUN CU

Page 21

- 12 -HeatingVOLT ITEMTOTAL INPUT kWTOTAL RUN CURRENT APOWER FACTOR %START CURRENT APEH-7240VPEH-8 20415VCOMPRESSOR INPUT kW RUN CURRENT

Page 22

- 13 -HeatingVOLT ITEMTOTAL INPUT kWTOTAL RUN CURRENT APOWER FACTOR %START CURRENT APEH-7240VPEH-8 20415VCOMPRESSOR INPUT kW RUN CURRENT

Page 23

- 14 -SELECTION PROCEDURE1. Model Selection (With actual examples)First step, to select the approximate model:Based on the cooling load and the coolin

Page 24

At 26˚CDB, 19˚CWB of Indoor,Q = 21.3, SHC = 16.3, T/I = 8.3Therefore, when air flow is 77(CMM)Q = 21.3 ✕ (1+(1.025 - 1.0) ✕ 7/10*) 21.7(kW)SHC = 1

Page 25

OUTDOOR DB ˚CINDOOR INDOOR 20.0 25.0 30.0 35.0 40.0DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW

Page 26

OUTDOOR WB ˚CINDOOR-10.0 -5.0 0.0DB ˚C Q kW Q kW Q kW T/I kWOUTDOOR WB ˚CINDOOR5.0 10.0 15.0DB ˚C Q kW Q kW Q kW T/I kW15161718192021222324252627

Page 27

OUTDOOR DB ˚CINDOOR INDOOR 20.0 25.0 30.0 35.0 40.0DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW

Page 28

- 1 -CONTENTSSAFETY FOR USE ------------------------------------------------------2A COMPLETE LINE UP ------------------------------------------------

Page 29

OUTDOOR DB ˚CINDOOR-5.0 0.0 5.0 10.0 15.0DB ˚CWB ˚C Q kW SHC kW SHF T/I kW Q kWSHC kWSHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q

Page 30

PE-8MYC-EUPEH-8MYA-EUAIR VOLUMECMM 60 70 80L/S 1,000 1,167 1,330COOLINGCAPACITY 0.976 1.0 1.025SHC 0.963 1.0 1.044TOTAL INPUT 0.991 1.0 1.00921.3 14.

Page 31

PE-8MYC-EUPEH-8MYA-EUAIR VOLUMECMM 60 70 80L/S 1,000 1,167 1,330COOLINGCAPACITY 0.976 1.0 1.025SHC 0.963 1.0 1.044TOTAL INPUT 0.991 1.0 1.0090.69 0.6

Page 32

PE-8MYC-EUPEH-8MYA-EUAIR VOLUMECMM 60 70 80L/S 1,000 1,167 1,330COOLINGCAPACITY 0.976 1.0 1.025SHC 0.963 1.0 1.044TOTAL INPUT 0.991 1.0 1.00921.3 14.

Page 33

PE-8MYC-EUPEH-8MYA-EUAIR VOLUMECMM 60 70 80L/S 1,000 1,167 1,330COOLINGCAPACITY 0.976 1.0 1.025SHC 0.963 1.0 1.044TOTAL INPUT 0.991 1.0 1.0090.69 0.6

Page 34

PE-10MYC-EUPEH-10MYA-EUAIR VOLUMECMM 90L/S 1,5501001,660COOLINGCAPACITY 1.0 1.035SHC 1.0 1.037TOTAL INPUT 1.0801,3300.9770.9680.991 1.00527.8 19.6 0.7

Page 35

PE-10MYC-EUPEH-10MYA-EUAIR VOLUMECMM 90L/S 1,5501001,660COOLINGCAPACITY 1.0 1.035SHC 1.0 1.037TOTAL INPUT 1.0801,3300.9770.9680.991 1.0050.69 0.69 0.6

Page 36

PE-10MYC-EUPEH-10MYA-EUAIR VOLUMECMM 90L/S 1,5501001,660COOLINGCAPACITY 1.0 1.035SHC 1.0 1.037TOTAL INPUT 1.0801,3300.9770.9680.991 1.00527.8 19.6 0.7

Page 37 - OPERATION RANGE

PE-10MYC-EUPEH-10MYA-EUAIR VOLUMECMM 90L/S 1,5501001,660COOLINGCAPACITY 1.0 1.035SHC 1.0 1.037TOTAL INPUT 1.0801,3300.9770.9680.991 1.0050.69 0.69 0.6

Page 38 - FAN PERFORMANCE

OUTDOOR DB ˚CINDOOR INDOOR 20.0 25.0 30.0 35.0 46.0DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW

Page 39 - PEH-20MYA-EU

SAFETY FOR USE- 2 - fire may result. If you need to have the unit Ask your dealer or specialized subcontractor for installation.For installation, con

Page 40 - Sectional plan of V-belt

OUTDOOR DB ˚CINDOOR INDOOR -5.0 0.0 5.0 10.0 15.0DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW S

Page 41 - SOUND DATA

42.6 29.8 0.70 13.2 41.2 29.3 0.71 13.9 39.8 28.7 0.72 14.8 38.4 28.0 0.73 15.8 36.6 27.1 0.74 16.944.0 27.4 0.62 13.5 42.6 26.9 0.63 14.1 41.2 26.1 0

Page 42 - OUTLINE DIMENSIONS

PEH-15MYA-EU AIR VOLUMECMM 120 140 160L/S 2,000 2,334 2,660COOLINGCAPACITY 0.976 1.0 1.025SHC 0.963 1.0 1.044TOTAL INPUT 0.991 1.0 1.0090.69 0.69 0.6

Page 43 - (Bottom side)

OUTDOOR DB ˚CINDOOR INDOOR 20.0 25.0 30.0 35.0 46.0DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW

Page 44 - PE(H)-20

OUTDOOR DB ˚CINDOOR INDOOR -5.0 0.0 5.0 10.0 15.0DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW S

Page 45 - (Upper blow)

55.6 39.2 0.71 17.5 54.0 38.4 0.71 18.4 52.2 37.4 0.72 19.7 50.2 36.2 0.72 21.0 47.8 35.3 0.74 22.757.8 36.4 0.63 17.7 56.2 35.7 0.64 18.6 54.2 34.6 0

Page 46 - (Side blow)

PEH-20MYC-EU AIR VOLUMECMM 160 180 200L/S 2,660 3,000 3,320COOLINGCAPACITY 0.976 1.0 1.025SHC 0.963 1.0 1.044TOTAL INPUT 0.991 1.0 1.0090.69 0.69 0.6

Page 47 - PUH-15,20

- 36 -OPERATION RANGEThe range of working temperatures is as below.Make sure which unit you are using and confirm the range of application.NoteAs an a

Page 48 - Duct work is local supply

- 37 -FAN PERFORMANCEPEH-5MYA-EUPE-8MYC-EUPEH-8MYA-EUPE-10MYC-EUPEH-10MYA-EU4035 45 50 55Recommended RangeInternal SP450400350300250200150100504504003

Page 49 - WIRING DIAGRAMS

- 38 -4006008001000200(Pa)Fan speed(rpm)110 120 130 140 150 160 170Recommended Range0Total static pressureAir flow (CMM)standard point5006007008009001

Page 50 - PE-8,10MYC-EU (STANDARD)

- 3 -The gas may ignite or explode when the gas leaks and collects in surround of the unit.The erroneous operation of air conditioner may beinduced by

Page 51 - PE-15MYC-EU (STANDARD)

- 39 -Pulley outside dimensions are shown below: (Unit : mm)(1) Shape of belt groove(2) Shape of motor pulley boss (Unit : mm)ear1r3fwL0r2r2KK0øP.C16.

Page 52 - PE-20MYC-EU (STANDARD)

- 40 -SOUND DATAIndoor unitsSound LevelsOCTAVE BAND FREQ. HzMODELSPL63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz63Hz 125Hz 250Hz 500Hz 1000Hz 20

Page 53 - PE-7MYC-EU

- 41 -OUTLINE DIMENSIONS131 200 19995152 156AIR INLET DUCTFLANGEHOLES:24- 3.134110210431130130130130130130130130313442042815157050530650130130424240

Page 54 - PE-8,10MYC-EU

- 42 -PE(H)-104040131 200 1995301565065015 15344204242130 130HOLES:26- 3.1AIR INLET DUCTFLANGE3413021046666 130130130130130130130130130DRAIN:Rc 1280

Page 55

- 43 -PE(H)-2081504089.59016790269.51513021 1170=130X9 211513044 1560=130X12 4411012122614240 55620 63631940252519931301301306005361587361546220736706

Page 56

- 44 -Hole : ø15REFRIGERANT PIPEHoles :4-12X20Holes : 2-ø15REFRIGERANT PIPEAIR OUTLETAIR INLETAIR INLETCABLE ENTRYSERVICE PANEL7584182175422752754221

Page 57

- 45 -PU-157816975857517050232312301070998852429981377211371046AIR INLETNo.1No.2AIR INLETAIR INLETAIR OUTLETPOWER SUPPLYCABLE ENTRY ø43REFRIGERANT PIP

Page 58

- 46 -PU-20PUH-15,2030No.1No.281756475392801601717203699885213961801199635 464 464 35AIR OUTLETPOWER SUPPLYCABLE ENTRY ø47CONTROLCABLE ENTRY ø27REFRIG

Page 59

- 47 -In the case of installation are shown below, it is possible to use the unit by connecting the duct.However, the pressure loss must be 30Pa (3mmA

Page 60

- 48 -WIRING DIAGRAMSCR2GRAYCHF3(3.15A)52CCZ3049C52C15TB5BLUECZ21463H51F2CZ2CZ3051CC5C4MC123BLACKREDMF3WHITE52C51C32151F2WHITEMF2REDREDWHITEBLACKBLACK

Page 61 - PUH-5MYE-EU···50A

- 4 -A COMPLETE LINE UPIndoor unitPEH-5kcal/h12,400Cooling capacityBtu/h49,150kW14.4kcal/h12,400Heating capacity(PEH only)Btu/h49,150kW14.4PE(H)-71

Page 62 - PEH-7MYA-EU (STANDARD)

- 49 -CR2GRAYCHF3(3.15A)F1(3.15A)(3.15A)52CCZ3049C52C15TB5BLUECZ21463H51F2CZ2CZ3051CC5C4MC123BLACKREDMF3WHITE52C51C32151F2WHITEMF2REDREDWHITEBLACKBLAC

Page 63 - PEH-8,10MYA-EU (STANDARD)

- 50 -PE-15MYC-EU (STANDARD)OUTDOORINDOOR UNITOUTDOOR UNITContactor (fan O/D)52F2Timer 2Over current relay(fanO/D)51F2Auxiliary relay (fan)30FZSurge k

Page 64 - PEH-15,20MYA-EU (STANDARD)

- 51 -PE-20MYC-EU (STANDARD)OUTDOORINDOOR UNITOUTDOOR UNIT52F252C2C15252F1BLACKWHITERED52F251F2BLACKBLACKWHITEREDREDMF2WHITE123C132151F3C2BLACKREDMF3W

Page 65 - PEH-5MYA-EU

- 52 -OUTDOORTM(3MIN)TMCR1CR2GRAYCH52FFZFZ3052FBLUE30FZF3(3.15A)51C63H51F2CZ2CZ30CZ3052CCZ115CZ21449C52CGRAYGRAYBLUEBROWNREDC1C1421SW2(FIELD SUPPLY)JU

Page 66 - PEH-7MYA-EU

- 53 -OUTDOOR(3MIN)TMTMCR1CR2GRAYCHF3(3.15A)(3.15A)F3(3.15A)52CCZ3049C52C15TB5BLUECZ21463H51F2CZ2CZ3051C220240V24VACACTrTB4TB423FZF2CZ130FZ52F52F14RED

Page 67 - PEH-8,10MYA-EU

- 54 -OUTDOORINDOOR UNITOUTDOOR UNITNote:1.The dotted lines show field wiring. 2.The figure in the parentheses show field supply parts. 3.Colo

Page 68 - Caution

- 55 -OUTDOORINDOOR UNITOUTDOOR UNITTimer (Anti short cycle.)TMContactor (fan O/D)52F2Timer 2Over current relay(fanO/D)51F2,3Auxiliary relay (fan)30FZ

Page 69

- 56 -PE-7MYC-EU(SPECIAL ORDER : LOW AMBIENT COOLING)Note:1.The dotted lines show field wiring. 2.The figure in the parentheses show field supply

Page 70

- 57 -PE-8,10MYC-EU(SPECIAL ORDER : LOW AMBIENT COOLING)Note:1.The dotted lines show field wiring. 2.The figure in the parentheses show field supp

Page 71 - PEH-15,20MYA-EU

- 58 -31C3C351F126L131C8C826L2Thermostat (freeze protection)26L1,2HOUTDOORINDOOR UNITOUTDOOR UNITThermostat (ambient temp.)26DContactor (fan O/D)52F2T

Page 72 - OPERATE

FEATURES- 5-DESCRIPTIONSHigh sensible cooling capacity.The sensible cooling capacity has been significantlyimproved through balanced optimised heat ex

Page 73 - PE-15MYC-EU PE-20MYC-EU

- 59 -HHHHOUTDOORINDOOR UNITOUTDOOR UNITOver current relay(fanO/D)51F2~F5Auxiliary relay (fan O/D) FZ2~7Thermostat (ambient temp.) 26D1~4Contactor (fa

Page 74

- 60 -PEH-5MYA-EU (STANDARD)MCOUTDOORConnectorSurge killerCR1,2Contactor (fan O/D)X2,3 Auxiliary relay (defrost)T1 Timer (defrost)Note:1.The dotted li

Page 75 - REFRIGERANT SCHEMATICS

- 61 -PEH-7MYA-EU (STANDARD)CR2GRAYX1X1C63C6113C7CHF3(3.15A)X1X252CCZ30C726D221T1S426D1X2X3X1 X2X3T149C52C1315HZ2TB5BLUECZ21463H51F2CZ2CZ3051CHZ2C5C4M

Page 76 - SAFETY & CONTROL DEVICES

- 62 -PEH-8,10MYA-EU (STANDARD)CR2GRAYX1X1C63C6113C7CHF3(3.15A)F1(3.15A)(3.15A)X1X252CCZ30C726D221T1S426D1X2X3X1 X2X3T149C52C1315HZ2TB4 (In case of PU

Page 77 - PEH-7,8,10MYA-EU

- 63 -PEH-15,20MYA-EU (STANDARD)Timer 2CR1 3 Surge killerOver current relay(fanO/D)51F2,3Auxiliary relay (fan)30FZContactor (fan O/D)X3 6 Auxiliar

Page 78 - SPECIAL ORDER

- 64 -PEH-5MYA-EUSPECIAL WIRING : ANTI SHORT CYCLE TIMER.,(PROTECT FOR COOL AIR BLOW. )OUTDOORMCOUTDOOR52FHigh-pressure switch63HInternal thermost

Page 79 - PHYSICAL DATA

- 65 -PEH-7MYA-EUSPECIAL WIRING : ANTI SHORT CYCLE TIMER.,(PROTECT FOR COOL AIR BLOW. )Auxiliary relay (defrost)Contactor (fan O/D)Timer (Anti sho

Page 80 - [EVAPORATOR]

- 66 -PEH-8,10MYA-EUSPECIAL WIRING : ANTI SHORT CYCLE TIMER.,(PROTECT FOR COOL AIR BLOW. )OUTDOOROUTDOOR(3MIN)TMTM1716X31717X31616CR1CR2GRAYX1X1C6

Page 81 - [ENCLOSURE AND FRAME]

- 67 -OUTDOORINDOOR UNITOUTDOOR UNITNote:1.The dotted lines show field wiring. 2.The figure in the parentheses show field supply parts. 3.Colo

Page 82 - 1-EU PUH-8MYC1-EU PUH-8MYE-EU

- 68 -PEH-7MYA-EU(SPECIAL ORDER : LOW AMBIENT COOLING)Note:1.The dotted lines show field wiring. 2.The figure in the parentheses show field supply

Page 83 - 1-EU PUH-8MYE-EU

- 6-TYPICAL INSTALLATION EXAMPLEMECHANICAL SPECIFICATIONSGeneral All units are factory assembled, piped, internally wired. They are also tested and c

Page 84

- 69 -PEH-8,10MYA-EU(SPECIAL ORDER : LOW AMBIENT COOLING)Note:1.The dotted lines show field wiring. 2.The figure in the parentheses show field sup

Page 85 - 1-EU PUH-10MYE-EU

- 70 -FZ7FZ4FZ3FZ2FZ6HHHHINDOOR UNITOUTDOOR UNITThermostat (ambient temp.)Auxiliary relay (fan O/D)FZ2~7Contactor (fan O/D)52F2~726D5~8Timer 2CR1~3 Su

Page 86

- 71 -ELECTRICAL OPERATION FLOW CHARTSSTARTPOWER ON52C ONMC OPERATEMF2, 3 OPERATESERVICE CALL23WA ON?SAFETY DEVICE OFF?NOYESYES30FZ,

Page 87

- 72 -STARTPOWER ON52C1 ONMC1 OPERATEMF2 OPERATE23WA ON?No.1 SAFETY DEVICE OFF?NOPASS THE 3 MIN?NOYESYES30FZ,30CZ1,2 ON (SELF HOLD)SER

Page 88 - Outdoor unit

- 73 -STARTPOWER ON52C1 ONMC1 OPERATEMF2 OPERATE52C2 ONMC2 OPERATEMF3 OPERATE26D1 4 ONX1,2,5,6 ONX3,4 ON

Page 89

Strainer Evaporator Ball valve Strainer High pressure switch Check joint 4-Way valveAccumulator Muffler Check joint Check va

Page 90 - 300 over

- 75 -SAFETY & CONTROL DEVICESITEM NO.PE-7MYC-EUPU-7MYC1-EUPE-8MYC-EUPU-8MYC1-EUPE-10MYC-EUPU-10MYC1-EUCOMPRESSOR OVER CURRENT RELAY 51C 19.0A 22.

Page 91 - Service Panel

- 76 -PEH-7MYA-EUPUH-7MYC1-EUPEH-8MYA-EUPUH-8MYC1-EUPUH-8MYE-EUPEH-5MYA-EUPUH-5MYE-EUPEH-10MYA-EUPUH-10MYC1-EUPUH-10MYE-EUCOMPRESSOR INTERNAL THERMOST

Page 92 - Indoor unit

- 77 -SPECIAL ORDERDescriptionPEH-5MYAPEH-5MYA-EU--PEH-7MYAPEH-7MYA-EUPE-7MYCPE-7MYC-EUPEH-8MYAPEH-8MYA-EUPE-8MYCPE-8MYC-EUPEH-10MYAPEH-10MYA-EUPE-10M

Page 93 - Lifting method

- 78 -PHYSICAL DATAPRODUCT]PACKAGE AIR COOLED HEATPUMP UNITS Product typePE SERIES Product number : Indoor unit

Page 94 - Piping connection

- 7 -MODEL-DESIGNATION BREAKDOWNPE-10 MYC1Design SequenceElectrical SupplyCompressor HorsepowerSeries Number5 = 5 HP7 = 7 HP8 = 7.5 HP10= 10 HP15=

Page 95 - Unit side

- 79 -Product number Indoor unit Outdoor unit[INDOOR AIR CIRCUIT] Number of blowers

Page 96 - Refrigerant piping

- 80 -Product number Indoor unit Outdoor unitPE-7MYC-EUPU-7MYC1-EUPE-8MYC-EUPU-8MYC1-EUPE-10MYC-EUPU-10MYC1-EUPE-15MYC-EUPU-15MYC1-EUPE-20M

Page 97 - Additional refrigerant charge

- 81 -PEH-5,7,8MYA-EUPRODUCT]PACKAGE AIR COOLED HEATPUMP UNITS Product typePEH SERIES Product number : Indoor unit

Page 98 - Drain piping

- 82 -Product number Indoor unit Outdoor unit[INDOOR AIR CIRCUIT] Number of blowers Diameter of blowers Width of blowers Blower drive F

Page 99 - Side blow

- 83 -Product number Indoor unit Outdoor unit[ENCLOSURE AND FRAME] height Dimension width Indoor unit Outdoor unitdepth he

Page 100 - Upper blow

PRODUCT]PACKAGE AIR COOLED HEATPUMP UNITS Product typePEH SERIES Product number : Indoor unit Outdoor unit Cool

Page 101 - PE(H)-7:Single phase

- 85 -Product number Indoor unit Outdoor unit[INDOOR AIR CIRCUIT] Number of blowers Diameter of blowers Width of blowers Blower drive F

Page 102

- 86 -Product number Indoor unit Outdoor unit[ENCLOSURE AND FRAME] height Dimension width Indoor unit Outdoor unitdepth he

Page 103 - (PE(H)-15,20 only)

- 87 -INSTALLATIONSpace required around unit.Indoor unit1.Dimension of the unit and space necessary for sevicing.Outdoor unitSecure enough space neces

Page 104 - Obstacle blocking air inlet

- 88 -PU(H)-7,8, 10 (Upper blow)(1) At a single installationThe obstacle is on the outlet side. (Fig 1)The obstacle is in three directions. (Fig 2,3)T

Page 105 - 3.Maintenance

- 8 -SPECIFICATIONSModel nameServicereferencePower supply IndoorOutdoorTotal cooling capacitySensible cooling capacitykWBtu/hkcal/h%Capacity stepRefri

Page 106 - 6-1 Transfer of installation

- 89 -500over300 over500overService-panelService-panel(2) Relation of unit when many set up unit. (Fig 3,4)Fig 3300 over300overAAAFig 4 All "

Page 107 - 6-5 Disposing of the unit

2. Preparation before installingPlease use the specified hanging bolt in any case.Hanging bolt is local supply.Please use the method below or use the

Page 108 - 7.Trouble shooting

- 91 -3. Installation of the unit.Indoor unitPlease carry the packed until parallelly to installed place.Please install the unit before construction o

Page 109

- 92 - Canvas Duct Canvas DuctDuct earthDuct earthDuctDuctOutletInlet Duct-work length 850mm or moreDrain panProvide canvas flexible ducting between u

Page 110

- 93 -Piping connectionPlease follow the following procedures, during the piping connection work is carried out.If the procedures are not followed pro

Page 111

- 94 -In case of Flare, Flange type(1) Open the ball valve cap before cutting the by-pass tube.(Fig.1)(2) Check the ball valve section is completely c

Page 112 - 1-6.Trouble shooting

- 95 -Extension piping and installation parts are field supply.Perform the work only after carefully reading theappropriate instructions.Install the u

Page 113 - OUTDOOR UNIT)

- 96 -Airtight testEvacuationAirtight test should be made by pressurizing nitrogen gas to 3Mpa.For the test method, refer to the following figure.(Mak

Page 114

- 97 -•Incline the drain piping to the outside (drain side) as shown in the figure below.•The outlet of the indoor unit drain pipe is Rc1.•After compl

Page 115 - DATA BOOK PE,PEH

- 98 -Construct the earth connection.All electrical work must be carried out by a suitable qualified electrical trades-person and inaccordance with lo