104
Notice
●
This function is only applicable to the indoor units connected to M-NET outdoor unit, but not
covering the indoor units connected to K-control outdoor unit and A-control outdoor unit.
● The indoor units under stopping or fan operation are out of the object for changeover.
When setting the [Typical air conditioner group assigning mode], the control will be
performed automatically with the [Auto-changeover mode] if the typical group is stopped
or under fan operation.
● Since the operation mode is determined by judging the status of each indoor unit
comprehensively under the [Auto-changeover mode], comfort may not be maintained at
the surrounding of the air conditioner partially. In such case, use a proper air conditioner
as the typical group under the [Typical air conditioner group assigning mode].
16.1.1 Auto-changeover mode
Under this mode, the difference of the set and inlet temperature of air conditioning groups (excluding the
group under fan operation or stopping) contained in a same changeover block is measured to assign points
to each group accordingly, and from this resultant total, the changeover mode (cooling/heating) is judged
for selection.
In order to determine the changeover mode with the consideration of a ratio of the number utilizing each air
conditioner, the points by temperature difference are weighted with the capacity value of the indoor unit.
16.1.2 Typical air conditioner group assigning mode
Judging for cooling/heating to be operated by viewing the set and inlet temperature of assigned air
conditioner groups within a changeover block for every 15 minutes, the indoor units within the changeover
block are switched over to cooling/heating for operation collectively.
When the points of each air conditioner group are multiplied with the weighting factor as below and
summed up, cooling is selected if the result stays on a positive number (over 1) while heating is selected if
it stays on a negative number (below -1).
Comments to this Manuals