8.4.4 Manual input of electric power consumption
The calculation method of manual input not connecting watt-hour meter is given below.
With this method, calculation is performed by employing the reading value of watt-hour meter without using
watt-hour meter or PLC itself.
Using “Charging ratio support software,”
enter the reading value of watt-hour
meter, and apportion it for each tenant.
Apportioning parameter file
(CVS format)
Preparation
of bill
G-50A
Collects and stores the following operation data of air
conditioners.
1 Indoor unit fan operation time
2 Indoor unit auxiliary heater operation time
3 Capacity saving ratio
4 Thermostat ON time
Calculating the apportioning parameter based on the data collected from G-50A
PC for centralized control
(Integrated software)
(1) Standard charge
This method can not process the standard charge as its sole function is to calculate air conditioning
charge based on the operation data. The standard charge should be added by the user additionally.
(2) Air conditioner charge
The air conditioning charge of each tenant can be calculated by using “Charging ratio support software
(EXCEL)” locating in the Integrated software install CD-ROM.
For the parameters required to calculate the charge, use “Apportioning parameters” and “Charging
ratio” explained in the Items 8.4.2 and 8.4.3.
By employing the file prepared by the integrated software based on these parameters (CSV file) and the
manual input of the electric power consumption of indoor/outdoor units, the air conditioning charge per
charge block (tenant) can be calculated by using a calculation software like “Charging rate support software.
(3) Apportioning parameters of outdoor unit
As explained in the item 8.4.2, calculate the value by using the indoor unit rated capacity for each
indoor unit per charging time frame, and total the value multiplied by the unit price for the charging
blocks, and then calculate a ratio to the total of all blocks.
Apportioning parameter =
Integrated value of indoor unit capacity control level (Capacity saving ratio or thermostat ON time) ×
Charging parameter of indoor unit rated capacity = Σ (Apportioning parameter × Unit price)
Charging ratio [%] =
(4) Apportioning parameters of indoor unit
As outlined in the item 8.4.1, calculate by using the rated electric power of the fan and auxiliary heater
of indoor unit per charging time frame and sum up the value multiplied by the unit price for charging
block, and calculate a ratio to the total of all blocks. For the indoor unit without auxiliary heater, amount
of “ON time of auxiliary heater × auxiliary heater electricity power consumption” will be zero.
Appor
tioning parameter = Operation time of indoor unit fan × Rated power consumption + ON time of
auxiliary heater × Auxiliary heater electricity power consumption
Charging par
ameter = Σ (Apportioning parameter × Charging unit price)
Charging r
atio [%] =
Total charging parameter of relative block
Total charging parameter of all blocks
Total charging parameter of relative block
Total charging parameter of all blocks
Figure 8-11 Mechanism of electric power manual input