the specified float level). Upon completion of the timer count, the Rectifier
output voltage shall return to the specified float voltage (typically 2.25 to 2.28
VDC/cell).
4.2.4. Battery Temperature Compensation
The UPS shall have, as standard equipment, a battery temperature
compensation function allowing the rectifier voltage to fold-back to a safe
value in the event the battery temperature reaches a pre determined dangerous
level.
4.2.5. DC Breaker
The DC input shall be protected by a DC Breaker that shall also include
circuitry to prevent wrong sequencing during startup or shutdown of the UPS
system. The DC Breaker shall be provided as standard equipment.
4.2.6. Ripple voltage
The DC(battery) buss rms ripple voltage shall be less than 1% of the UPS’
nominal DC voltage level at 100% load. This shall provide for maximum
battery life.
4.3. Inverter
4.3.1. General
The Inverter shall generate AC power that is derived from DC power
supplied from the Rectifier or the system battery. The Inverter shall be
capable of providing rated output as stated in section 3.4 while operating
from any DC voltage within the battery operating range. The Inverter shall
utilize the following technologies:
a. Solid state PWM controlled IGBT power transistors switching at 10
kHz. Switching shall be defined as IGBT turn on and turn off rate.
Doubling of frequency at inverter output shall not be considered as the
true switching frequency.
b. DSP based control logic.
4.3.2. Voltage Regulation