Forced air cooling shall be provided to allow all components to operate within their
rated temperature window. Thermal relays, using a latched contact which is capable
of being reset, shall be used as overload protection to all cooling fans. Each fan
shall employ a separate thermal relay. All air inlets use washable air filters that
shall be removable from the front of the UPS without exposure to any electrical
hazard. Air filters shall be door mounted to prevent floor dust from being sucked
into the unit. Bottom mount air filters shall not be accepted.
9.4. Printed Circuit Boards
All printed circuit boards shall be conformally coated against corrosive vapors and
to hermetically seal them.
9.5. Busbar
All busbar used for conductivity within the UPS shall be designed with
COPPER ONLY.
Aluminum not acceptable
9.6. Factory Test Report
All UPS units shall come equipped with one (1) factory test report included in the
UPS.
The factory test report shall include the following:
A. Series/kVA
B. Serial Number
C. Date of test
D. Approved by/Inspected by/Tested by
E. Inspection of construction
F. Checking of wiring (Black/Red marking on each connection point)
G. Grounding Continuity
H. Insulation strength test
I. Control Circuit Operation
J. Measurement of steady state characteristics (Voltage/ current/
efficiencies)
K. Transient characteristics (0-100% step load, without batteries/ voltage
fluctuation)
L. Overload Testing