8. OPTIONAL EQUIPMENT
8.1. Remote Status Alarm Panel (RSAP)
The UPS manufacturer shall offer a Remote Status Alarm Panel which shall not
allow any control over the UPS. The RSAP shall have, as standard equipment, a
battery backup feature allowing it to continue monitoring UPS status
conditions during power outage situations. Ride through shall be for a minimum
of 8 hours. The RSAP shall act only as an annunciation panel providing the
following alarms/indications as a minimum:
a. Rectifier on
b. Load on Inverter
c. Load on Bypass
d. UPS Failure
e. Output Overload
f. UPS in battery back-up mode
g. Low battery while in back-up mode
9. MECHANICAL DESIGN
9.1. Enclosure
The UPS shall be equipped with standard forklift provisions to allow ease of
installation using conventional lifting/moving equipment. All UPS enclosures shall
require a special tool or screw driver to allow internal access.
9.2. Serviceability
The UPS shall have front access only for maintenance or service. Side access or rear
access shall not be accepted. The UPS shall be designed such that its rear can be
pressed against a back wall and its sides can be pressed against side walls.
9.3. Ventilation