4.3 Wiring of the Control Circuit
The following picture shows the arrangement of the terminal for the control circuit of the inverter.
Wiring
16 MITSUBISHI ELECTRIC
RUN
RUN
SET
MODE
PU
EXT
PU
+
-
EXT
STOP
RESET
SINK
A
B
C
SOURCE
PC
SE
RUN
AM
RH
RM
RL
STR
SD
10
2
5
4
PE SE RUN 10 2 5 4
SD
A
SD
B
STF
C
STR RL RM RH AM
Signal Terminal Terminal name Description
Input signals
Contact input
STF Forward rotation start
The motor rotates forward, if a signal is applied to termi
-
nal STF.
When the STF and STR signals are turned on simulta
-
neously, the stop command is given.
STR Reverse rotation start
The motor rotates reverse, if a signal
is applied to terminal STR.
When the STF and STR signals are
turned on simultaneously, the stop
command is given.
Input terminal
function selec-
tion (Pr. 60 to Pr.
63) changes the
terminal func-
tions.
RH, RM, RL Multi-speed selection
Up to 15 different output frequencies
can be preset; for the speed com-
mands the following priorities apply:
Jog, speed selection (RH, RM, RL,
RX) and AU.
Common
SD
Common sink for contact in
-
put/reference potential
A determined control function is activated, if the corre-
sponding terminal is connected to the terminal SD. The
SD terminal is isolated from the digital circuits via
optocouplers.
The terminal is isolated from the terminals 5 and SE.
PC
24V DC output and common
source for contact input/refer
-
ence potential
24V DC / 0.1A output via PC-SD
In sink logic, when activated by open collector transistors
(e.g. PLC) the positive pole of an external power supply
has to be connected to the PC terminal.
In source logic, the PC terminal serves as common refer
-
ence point for the control inputs.
Analog
Setting value specification
10
(output volt
-
age 5V DC)
Voltage output for
potentiometer
Output voltage 5V DC
Max. output current 10mA.
Recommended potentiometer: 1k, 2W linear,
multiturn potentiometer
2
Input for frequency setting-
value signal
The voltage setting value 0–5 (10) V is applied to this ter
-
minal. The voltage range is preset to 0–5V.
(Parameter 73). The input resistance is 10k; The maxi
-
mum permitted voltage is 20V.
5
Reference point for frequency
setting value signal
Terminal 5 is the reference point for all analog setting val
-
ues (Terminal 2 and 4) and for the analog output signal
AM. The terminal is not isolated from the terminals SD
and SE and must not be earthed.
4
Input for current
setting value signal
0/4–20mA DC
The current setting value signal (0/4–20mA DC) is ap
-
plied to this terminal. The input is active only if the AU sig
-
nal is set. The function of the AU signal is assigned via
parameters 60 to 63. The input resistance is 250,the
max current is 30mA. By default, this signal is set to 0Hz at
4mA and 50Hz at 20mA.