Mitsubishi FR-S500 Installation Manual Page 25

  • Download
  • Add to my manuals
  • Print
  • Page
    / 28
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 24
Error message
Meaning Description Remedy
Display
FR-PU04
LED-
display
PU Leave
Out
Parameter unit
connection error
A connection error between in
-
verter and external parameter
unit occurred during operation.
This alarm is only returned, if Pr.
17 is set to “1”.
Check the connection of the pa
-
rameter unit.
Automatic re
-
start retry ex
-
ceeded
After activation of a protective
function the inverter failed to be
restarted automatically within
the number of retries specified
in Pr. 67.
Remedy the actual cause of the
originary protective function.
CPU
Fault
CPU error
Failure on CPU printed circuit
board.
Contact the MITSUBISHI ELEC
-
TRIC customer service
PS
Inverter was
stopped via con
-
trol panel or PU
STOP key on the control panel
or PU was pressed during exter
-
nal operating mode.
Check Pr. 75.
OL
Overcurrent
during
acceleration
If a current of more than 150 %
of the rated inverter current
flows in the motor, this function
stops the increase of the fre
-
quency until the overload cur
-
rent reduces to prevent the in
-
verter from resulting in
overcurrent shut-off.
Change the acceleration/deceler
-
ation time. Increase the stall pre
-
vention operation level via Pr. 22.
Disable the stall prevention via Pr.
21. Check whether the torque
boost in Pr. 0 is set higher than re
-
quired.
Overcurrent
during constant
speed
If a current of more than 150 %
of the rated inverter current
flows in the motor, this function
lowers the frequency until the
overload current reduces to pre-
vent the inverter from resulting
in overcurrent shut-off.
Overcurrent
during decelera-
tion
If a current of more than 150 %
of the rated inverter current
flows in the motor, this function
stops the decrease of the fre-
quency until the overload cur-
rent reduces to prevent the in-
verter from resulting in
overcurrent shut-off.
oL
Overvoltage
during
deceleration
If the regenerative energy of the
motor exceeds the brake capac
-
ity of the inverter, this function
stops the decrease of the fre
-
quency to prevent overvoltage
shut-off. When the regenerative
energy has reduced, decelera
-
tion resumes.
Increase the deceleration time
using Pr. 8 “deceleration time”.
Undervoltage
The power supply voltage is too
low.
Check the power supply
voltage.
Write error
Write was performed with “1”
(write disable) set in Pr. 77 or
frequency jump setting range
overlapped or parameter write
was performed via the control
panel although it was not write
enabled.
Check the settings of Pr. 77, 31 to
36, and n17.
OPERATOR
ERR
Write error
Write was performed during op
-
eration or in the external opera
-
tion mode or an attempt was
made to change the operation
mode set by an operation com
-
mand via Pr. 79.
Stop operation before changing
settings.
Select PU (parameter unit) oper
-
ation mode.
Calibration error
Analog input bias and gain are
set too closely.
Check the settings of Pr. C3, C4,
C6, and C7.
The current limit value (Pr. 22) can be changed. By default, it is set to 150%.
Protective Functions
FR-S 500 EC/ECR 25