Mitsubishi G-50A Installation Manual Page 30

  • Download
  • Add to my manuals
  • Print
  • Page
    / 110
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 29
26
(4) Recommended circuit example
(A)Level signal
* S
pecial local arrangements are required for the relay, DC power supply (DC 12V, or DC 24V), and extension cables, etc.
* Please limit extension of the connection cable to 10 meters. (Please use cables of 0.3mm
2
or more)
* Please cut off any unused cable close to the connectors and be sure to insulate the cut parts using tape, etc.
(B)Pulse signal
Start/stop and
emergency stop
X1
DC power supply
Red
Maximally
10m
Local arrangement board
1
5
6
7
8
9
CN2
G-50A
Orange
X1
Operation
Stop
Prohibition
Permission
X1
X1
X2
X3
X4
X2
X3
X4
DC power supply
Red
Maximally
10m
Local arrangement board
1
5
6
7
8
9
CN2
G-50A
Orange
Yellow
Blue
Gray
5.2.2 External output signal function
(1) External output
When at least one air conditioning unit is operating, a [Abnormality occurrence] signal is output when
abnormalities occur in at least one air conditioning unit.
(2) External input interface specifications
The external input interface specifications are outlined in Table 5-4.
Even during an [Abnormality occurrence], the [Operating] signal is output.
(3) Recommended circuit example
Table 5-4 External input interface specifications
CN2
No. 1
No. 2
No. 3
Lead wire
Green
Black
Brown
Details of each terminal
External output common ground (external DC power supply ground)
Start/stop
Irregular/regular
* For the relays (X1, X2), please use those with the following specifications.
* Operating coil: DC 12V, DC 24V, power consumption: 0.9W or less
* Please make special arrangement to adjust the DC power supply to DC 12V or DC 24V depending on the relay used.
* Please be sure to use diodes at both ends of the relay coil.
* Please limit extension of the connection cable to 10 meters. (Please use cables of 0.3mm
2
or more)
* Please cut off any unused cable close to the connectors and be sure to insulate the cut parts using tape, etc.
X1
X2
L1
L2
X1
D1
X2
D2
DC power supply
Maximally
10m
Local arrangement board
1
2
3
4
CN2
G-50A
Green
Black
Brown
Notice
When using this device to start/stop or emergency stop the external input level, an
operation prohibition setting for the local remote controller is transmitted regardless of
whether function selection No. 4 is set for enabled or disabled of the prohibition setting.
Consequently, when using this device for start/stop or emergency stop of the external
input level, please do not perform any operation prohibition settings involving other
system controllers.