4.5.4 Setting for current limit SW (for SCM68YA, cooling only type)
¡ Locations to secure the bolts.
¡ Use M10-M12 for the retaining bolts.
¡ Secure it firmiy so the unit will not fall during earthquakes and from sudden gusts of wind.
¡ There are 3 holes in the bottom panel of
the outdoor unit to drain condensation.
1 Service panel
¡Remove the screws, and pull the panel toward the direction.
2 Top panel
¡Remove the panel when cheking the abnormal indicator LED
during the protective function.
This unit has a current limit default velue of Max.Amp (17.5A) to change
the default value, remove the front panel and set the switch fot the printed
circit board etc., according to the following instructions.
1 Changing the current limit to 11A.
Turn on the SW6 shown in the figure.
2 Changing the current limit to 8.5A.
Turn on the SW5 and SW6 shown in the figure.
Securing the Unit
Drainage
Removing the Outer Panel
2 Top panel
1 Service panel