(2) Connection of refrigerant piping
¡ The service valve corresponding to each indoor unit is as illustrated in the right figure.
¡ Regarding the change in the sizes of gas side pipes (usage of the variable joints); if a 3.2/
4.0/5.0 kW class indoor unit (gas side pipe 12.7) is going to be connected to the rooms A
and B service valves (9.52), or if a 2.2-2.8 kW class indoor unit (gas side pipe 9.52) is
going to be connected to the rooms C service valves (12.7), variable joints (1, 2) avail-
able as accessories must be applied to the gas side service valves.
[Examples of use of variable diameter joints]
Connection of indoor unit of Class 3.2 to A unit.
¡ Securely fit the copper packing between the service valve and the variable diameter joint to prevent shifting.
¡ Cover the pipes with tape so that dust and sand do not enter the pipe until they are connected.
[Connection of pipes]
¡ When connecting the pipes to the outdoor unit, be careful about the discharge of fluorocarbon gas or oil.
¡ Make sure to match the pipes between the indoor unit and the outdoor unit with the correct service valves.
(1) Preparations
¡ Remove the flare nut (from both
liquid and gas sides).
¡ Remove the flare nut (from both
liquid and gas sides).
¡ Fit the removed flare nut to the joint pipe, and then flare it.
A dimensions
Liquid side: ø 6.35:9 ~9.5dia
Gas side:
ø 9.52: 13.2 ~ 14dia
ø 12.7: 16.2 ~ 17dia
Gas
Gas
side
service
valve
Liquid
Liquid
side
service
valve
Service valve
for room C
Service valve
for room B
Service valve
for room A
ø12.7
ø9.52
ø9.52
ø6.35 pipe
ø12.7 pipe
Indoor unit
3.2 kW class
Liquid side operational valve (ø6.35)
Gas side service
valve (ø9.52)
Copper packing Variable diameter joint (ø9.52-ø12.7)
Service
valve for room A
Indoor
Remove
Push
Outdoor
Remove
Push
90+0.5˚
A
4.5.6 Refrigerant Piping
(1) Limit
The maximum permissible length of the refrigerant pipes for the outdoor units, and the maximum permissible height difference for
the outdoor units are as shown below.
* If the total length for all the rooms exceeds the length of chargeless refrigerant pipe, additionally charge with refrigerant accord-
ing the item 4.
¡The diameter of the refrigerant pipe:
¡Outdoor unit and the total connectable indoor units (class kW):
Lower installation spot of the indoor unit A
Upper installation spot of the indoor unit B
Maximum height difference of the indoor units C
Length for one indoor unit
Total length for all rooms
Length of chargeless refrigerant pipe*
SCM68ZA, SCM68YA
under 25m
under 40m
under 15m
under 10m
under 25m
30m
Height
difference
Liquid side
Gas side
2.2 · 2.5 · 2.8kW
ø 9.52 · t 0.8
3.2 · 4.0 · 5.0kW
ø 12.7 · t 0.8
ø 6.35 · t 0.8
Class of indoor unit (kW)
Diameter of joint pipe
A
B
C
Model
SCM68ZA
SCM68YA
Total of indoor units (class kW)
9.6kW
12.0kW