j. Automatic UPS restart and load pick-up (after system battery depleted;
AC restored).
k. Programmable external customer contacts (A-Type) dry contacts.
l. Touch screen person-machine interface.
m. Remote and Local Emergency Power Off (EPO).
n. Static Bypass Disconnect.
o. History graph of Kw, UPS events
2.1.6. Optional features:
a. Remote monitor panel.
b. Maintenance Bypass Switch (MBS).
c. Input Isolation Transformer.
d. Wall mounted or free standing DC cable landing cabinet.
2.2. Modes of Operation
The UPS shall be designed to operate continuously at rated capacity as an on-line,
automatic system in the following modes:
2.2.1. Normal - The inverter continuously supplies AC power to the critical load. The
rectifier converts commercial AC power to regulated DC power which then
serves as the inverter input and, simultaneously, as a float charge input to the
storage battery.
2.2.2. Emergency - In the event of a commercial AC power failure, the inverter shall
derive its input from the system battery, thus providing uninterrupted power to
the critical load. This transition shall be accomplished without any switching or
coupling, and with no interruption of power to the critical load from either a
failure or restoration of the commercial AC power.
2.2.3. Recharge - Subsequent to restoration of commercial AC power, the rectifier
shall automatically reactivate and provide DC power to the inverter,
simultaneously recharging the system battery. This occurs automatically and
without interruption to the critical load.
2.2.4. Bypass - In the event that the UPS must be taken off line due to an overload
condition or UPS failure, the critical load shall be transferred to the bypass
source via the static switch without interruption of power to the critical load. A
paralleling, wrap-around contractor shall be used to maintain the bypass source.
The static switch shall only be utilized for automatic emergency transfers. A re-
transfer from bypass to inverter shall be performed automatically in overload
conditions. A re-transfer shall be inhibited if satisfactory synchronization of the