7. WEB MONITORING FUNCTION
This web monitoring system monitors and operates air conditioner connected to central control SC-SL4-AE or
SC-SL4-BE from a web browser on your PC.
The following figure shows the basic system configuration. The SL4 central control connected to the air
conditioner is linked directly to the monitoring and operating PC.
The web monitoring system can monitor and operate the air conditioner by the group. It cannot monitor and
operate the units by the block.
• Specifications of PC
The PC to be used with this product is not provided with the system. You must prepare it separately.
The following describes the minimum performance requirements for the PC.
• CPU clock : Pentium 500 MHz or higher (2 GHz or higher is recommended)
• Memory : 512 MB or more (1 GB or more is recommended)
• Operating System and Web Browser
The following table shows the supported combinations of operating systems and web browsers.
If you want to use other combinations, contact your dealer.
Internet Explorer 8 Internet Explorer 9
Windows
®
XP
Windows Vista®
(SP1 or later)
Windows® 7
٤
٤
٤
٤
٤: Can be used, : Cannot be used
* Restart Internet Explorer regularly.
* Windows and Windows Vista are the registered trademarks of Microsoft Corporation in the United States and/or other countries.
2
Air conditioner
1
Central
control
Internet
Explorer
R
R
R
R
R
R
Air conditioner
17
Air conditioner
2
Air conditioner
18
Air conditioner
4
Air conditioner
20
Group 1
Group P +1
Group 2
Block 2
Group P
Group Q
Air conditioner
3
Air conditioner
19
Air conditioner
5
Air conditioner
21
Block 1
Monitoring and operating PC
Ethernet 10BASE-T or 100BASE-TX
Connection via a hub or direct connection
Air conditioner
P
Air conditioner
30
• A maximum of 16 air conditioners can be set up in one group.
• Do not use one remote control for different groups of air conditioner.
• A maximum of 9 groups can be set up in one block.
• A maximum of 16 blocks can be set up.
Air conditioner
1
R
Air conditioner
2
Air conditioner
4
2 puorG1 puorG
Air conditioner
3
R
: Remote control
PC Environments
Fig.4 Web monitoring system diagram