Mitsubishi MCFZ-A18WV Service Manual Page 29

  • Download
  • Add to my manuals
  • Print
  • Page
    / 52
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 28
2929
ACTUATOR CONTROL
9
MUZ-A18YV -
MUZ-A24YV -
MUZ-A26YV -
E1
E1
E1
Relation between main sensor and actuator.
9-3. Relation between main sensor and actuator
9-2. R.V. coil control
Heating
. . . . . . . . . . . . . . . .
ON
Cooling. . . . . . . . . . . . . . . . . OFF
Dry
. . . . . . . . . . . . . . . . . . . .
OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
ON
OFF
Outdoor fan
Compressor
5 seconds 15 seconds
ON
OFF
Compressor
Outdoor fan
R.V.coil
ON
OFF
ON
OFF
<COOL>
5 seconds
<HEAT>
5 seconds
9-1. Outdoor fan motor control
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
Discharge temperature thermistor
Indoor pipe temperature thermistor
Defrost thermistor
Fin temperature thermistor
Outdoor heat exchanger temperature
Purpose
Protection
Defrosting Protection
Defrosting
Protection
Protection
Compressor LEV
Outdoor
fan motor
4-way
valve
Sensor
Actuator
OB346A --1qxp 04.6.14 1:20 PM Page 29
Page view 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 51 52

Comments to this Manuals

No comments