7. External input/output function
* External signal input requires the external I/O adapter (Model: PAC-YG10HA-E) sold separately.
* Refer to Instalation Manual for detail.
7 - 1 External input function
(1) The function of external input
Emergency stop/normal, run/stop and prohibit/enable of local remote controller operation can be controlled for all
air conditioners by using a voltage (DC12V or DC24V) contact signal from an external source. (Select with the
function select setting.)
No. Function of external input signal
1 External input signal not used
2 Perform emergency stop with level signal
3
Perform ON/OFF operation with level sig-
nal
4
Perform ON/OFF operation, prohibit/per-
mit operation with pulse signal
Function
No.6 No.7
OFF OFF
OFF ON
ON OFF
ON ON
Remarks
During emergency stop, only ON/OFF of the central
controller and local remote controller's operation
will be prohibit.
Only the ON/OFF operation of the central controller
and the local remote controller will be prohibit.
Set the pulse width while the contact is ON to 0.5
to 1.0 second.
(2) Level signal and pulse signal
1Level signal
2Pulse signal
(3) Specification of external input interface
CN2
No.5
No.6
No.7
No.8
No.9
Lead wire
Orange
Yellow
Blue
Gray
Red
Emergency stop/normal
level signal
Emergency stop/normal input
Not used
Not used
Not used
Common (DC12V or DC24V)
ON/OFF level signal
ON/OFF input
Not used
Not used
Not used
ON/OFF, prohibit/permit
pulse signal
ON input
OFF input
Local remote controller
prohibit input
Local remote controller
permit input
(A) Level signal
1When the level signal is selected, the operation (only ON/OFF operation) for the central controller and the
local remote controller are prohibited (except during normal operation).
2When the emergency stop/normal operation signal is selected, the status will be changed from normal oper-
ation to emergency stop when the external input signal contact turns OFF to ON, and will be changed from
emergency stop to normal operation when external input signal contact turns ON to OFF.
Air conditioning units that came to an emergency stop will remain stopped after the emergency stop is can-
celled. Manually start up each unit to restore the previous operation.
3When ON/OFF input signal is selected, the status will be changed from OFF to ON when the external input
signal contact turns OFF to ON, and will be changed from ON to OFF when the external input signal contact
turns ON to OFF.
CONTACT ON CONTACT ON
CONTACT ON
CONTACT ON
CONTACT OFF
CONTACT OFF
CONTACT OFF
CONTACT OFF
OFF OFF
OFF OFF
ON
ON
Signal 1 (ON)
Signal 2 (ON)
0.5 ~ 1.0sec
0.5 ~ 1.0sec
Emergency
Normal
stop Normal
(Prohibit/permit is the same)