Mitsubishi G-50A Specifications Page 40

  • Download
  • Add to my manuals
  • Print
  • Page
    / 48
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 39
39
(B) Pulse signal
1Even if the ON signal is input during ON, the status will remain at the ON status.
2When the local remote controller is prohibited, the ON/OFF operation, operation mode selection and tempera-
ture setting from the local remote controller is prohibited.
3Set the pulse width (contact ON time) to 0.5 to 1.0 second.
7 - 2 External output function
(1)The function of external output
The "ON" signal is output when one or more air conditioner are in the ON operation.
The "Malfunction" signal is output when one or more air conditioner malfunctions.
(2)Specification of external output interface
1"ON" signal and "Malfunction" signal will both be output.
CN2
No.1
No.2
No.3
Lead wire
Green
Black
Brown
Description of each terminal
Common (0V)
ON/OFF
Malfunction/Normal
WT03945X02_En_P36-46 07.3.23, 8:14 PM39