12
LOW AMBIENT COOLING OPTION
PATENT PENDING
The low ambient cooling kit makes it possible to provide 100%
cooling capacity at outdoor temperatures down to -10
o
F while still
allowing full airflow at higher ambient temperatures and full heating
capacity if the unit switches to that mode
.
The kits are designed for use with the PUHY, PURY and PUHY-
HP modular outdoor units. The hood, which includes
an electronically controlled damper assembly, will modulate
its position automatically and, combined with the INVERTER–
driven fans, will provide optimum airflow at lower temperatures.
The specially designed wind deflectors will block unwanted
wind that could impede operation and, at the same
time will allow full airflow when required at higher ambient
temperatures or in heating mode. Another benefit of the
assembly is a more efficient defrost cycle when the unit is
operating in heating mode.
Complete Low Ambient Kit requires hood with control damper
assembly and wind deflectors.
Additional features
• Hood and wind deflectors constructed of 20 gauge
Hot-dipped galvanized G-90 steel
• Heavy-duty polyester-based powder paint finish
• Designed to work with both 208/230 and
460 3-phase units
• NEMA 4X control box protects electrical components
from the elements
• Kit easily connects to outdoor unit with plug–in
electrical connections
• Wind deflectors easily install with existing
(wire guard) fasteners
Mitsubishi Electric is the first
and only VRF manufacturer to offer a
low ambient cooling solution
for its 6–30 ton air source
outdoor units.
General features
Allows system to operate at 100% COOLING capacity at
reduced outdoor temperatures:
• PUHY Y-Series Outdoor Units –
(Now down to -10o FDB Outdoor Temp.)
• PURY R2-Series Outdoor Units –
(Now down to -10oFDB Outdoor Temp.)
• PUHY-HP H2i Y-Series Outdoor Units –
(Now down to 0o FDB Outdoor Temp.)
Components required
per outdoor unit(s)
For outdoor units with multiple modules, a minimum 1-3/16"
separation between the modules is recommended. If modules
are placed farther apart, than 15" apart, more than one set
of SWD-1 side wind deflectors may be needed. For multiple
units or module sets placed in a row, only one side wind
deflector kit (SWD-1) is needed to cover the two outside
module coil surfaces.