74
SYSTEM INTEGRATION: LONWORKS
®
AND BACNET
®
The CMCN supports integration with Building Management
Systems (BMS) via our LonWorks
®
and BACnet
®
interfaces.
LonWorks
®
Interface
The Mitsubishi Electric HVAC LonWorks
®
interface, LMAP03U,
supports up to 50 indoor units with a variety of network
variables on a per indoor unit basis. Input variables include,
but are not limited to: On/Off, Operation Mode, Fan Speed,
Prohibit Remote Controller, and Filter Sign Reset.
Output variables include but are not limited to: Model Size,
Alarm State, Error Code, and Error Address.
BACnet
®
Interface
The Mitsubishi Electric
HVAC BACnet
®
gateway,
BAC-HD150, is compliant with BACnet
®
/IP (ANSI/ASHRAE
135-2004) and is BTL
®
Listed. Each BAC-HD150 can support
up to 50 indoor units with a variety of object types. Operation
and monitoring points available include ON/OFF, mode, space
temperature set point, prohibition of remote controller functions,
error codes and alarms.