5. Initial setting
5 - 1 Shifting to initial setting menu
Shift to the initial setting menu by continuously pressing + (2 seconds or longer) on the user operation
menu screen. (Refer to section "3-2".)
Shift to the user operation menu by continuously pressing + (2 seconds or longer) on the initial setting
screen. (Refer to section "3-2".)
When group information is not saved, the following initial setting screen is displayed when power is turned on at
this controller.
5 - 2 M-NET address setting
(1) Select
6
"6 ADDRESS SETTING" (or
1
"1 ADDRESS SETTING").
(2) Set the controller address by pressing the
0
to
9
INS.
switches (000,201 ~ 250).
(3) When the
BACK
SCREEN
switch is pressed after setting, the screen returns.
When the controller is shipped from the factory, the address is set to "000".
(Always set the address to "000" When the K transmission converter is managed.)
MENU WED 15:29
1
ADDRESS
SETTING
2
FUNCTION
SETTING
4
GROUP
SETTING
PLEASE
SET
INITIAL
SETTING
3
IP
ADDRESS
SETTING
MENU WED 15:29
6
ADDRESS
SETTING
ADDRESS SETTING
7
FUNCTION
SETTING
8
IP
ADDRESS SETTING
M-NET ADDRESS: 000
NOTE: Observe the following precautions when this controller manages the M-NET models and K control
models by using the K transmission converter (PAC-SC25KAA).
Refer to the K transmission converter instruction manual for further details.
Address of this controller
Always set the address of this controller to "000".
Function select setting of this controller
Always set the No.3 function setting to ON.
Indoor unit address
Set all the M-NET models of indoor units from 001, next, set the address of the K control indoor
unit.
Indoor unit address
001 ~ M-NET indoor unit maximum address < K control indoor unit
minimum address ~ 050
* Assign the address of the smallest K-control indoor unit in the group as the group number.
Press the
BACK
SCREEN
switch to back
to the initial
setting menu.
Press the
6
switch
to select "6 ADDRESS
SETTING"
WT03945X02_En_P01-35 07.3.23, 8:13 PM25