16
NOTE ● When the indoor coil thermistor reads above 18°C, indoor fan operates at Very Low for 30 seconds.
● When the indoor coil thermistor reads 18°C or less, the indoor fan stops.
(3) Defrosting time chart
Defrost thermistor
3.1: or more
-3: or less
Outdoor 52C relay
(Compressor)
X62
(R.V.coil)
SR61
Outdoor fan
Defrost
counter
Indoor fan
Indoor vane
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Position 1
Set
Position
Max. 10 min.
30 sec.
15 sec.
30 sec.
5 sec.
Very Low
RT61
NOTE
OB266--1.qxp 01.4.13 10:31 AM Page 16