10-2-1. Troubleshooting check table
Before taking measures, make sure that the symptom reappears, for accurate troubleshooting.
No.
1
2
3
SymptomOperation indicator lamp Detection method
Checkpoint
0.5-second ON
0.5-second OFF
1-time flash
2.5-second OFF
Mis-Wiring
Serial sig-
nal
Outdoor
thermistor
Indoor coil
thermistor
After 3 minutes from power supply turns ON,
when serial signal is not received.
When serial signal from outdoor unit stops for
4 to 5 seconds.
<Thermistor short>
Thermistors are abnormal when they short
after compressor start-up.
<Thermistor open>
Thermistors are abnormal when they open
after compressor start-up.
• Refer to H "Check of outdoor
thermistor" on page 31.
• Refer to G "How to check
mis-wiring and serial signal
error" on page 30.
• Refer to G "How to check
mis-wiring and serial signal
error" on page 29.
Abnormal
point
Outdoor unit
does not
operate.
Room
tempera-
ture
thermistor
2-time flash
2.5-second OFF
Detect Indoor coil/room temperature
thermistor short or open circuit every 8
seconds during operation.
• Refer to the characteristics of
main indoor coil thermistor,
sub indoor coil thermistor,
and room temperature
thermistor on page 32 or 33.
Outdoor unit
does not
operate.
6-time flash
2.5-second OFF
Outdoor unit
does not
operate.
4
Outdoor
control
P.C. board
When it cannot properly read data in the
nonvolatile memory of the outdoor control P.C.
board.
• Check the outdoor control
P.C. board.
7-time flash
2.5-second OFF
Outdoor unit
does not run