INSTALLATION
10
2.3 Communication cable
When making a cable for the Modbus Plus protocol, make sure that each
end of the cable is terminated with the A5MBKT185 terminator connectors.
For nodes between the termination points, use the in-line connectors
(A5MBKT085). The cable should be a Modbus Plus standard cable
(490NAA271xxF).
Connect a wire from the ground terminal on the FR-A5NM to the
inverter Chassis to ensure proper grounding of the option board.
Makers of DB9 connectors, Schneider Automation:
• End Connector Part#: AS-MBKT-185 (light gray)
• Inline Connector Part#: AS-MBKT-085 (dark gray)
Figure 6 : Modbus connector