INTRODUCTION
3
Diagnostic LED Status Indicator
The green LED located next to the address DIP switch on the Modbus
Plus option top board provides indication of communication status. The
LED on the bottom board will be solid green if the option CPU acts
correctly.
The following describes the LED on the top board definitions.
Table 1
Green State of system
Flash every 160ms
Node is working normally. It is successfully
receiving and passing the network token.
Flash every 1s
Node is in the MONITOR_OFFLINE state. It
monitors the network link every 5 seconds
but is not transmitting.
2 flashes, off 2s
Node is in MAC_IDLE state. This node may
have a bad transmitter.
3 flashes, off 1.7s
Node is not receiving tokens. This indicates
that this node is the only active node on the
network or the receiver is bad.
4 flashes, off 1.4s Duplicate node address seen.