Symbol Terminal Name Description
Input signals
5
Frequency
setting input
common
Common terminal for the frequency setting signals
(terminals 2, 4) and indicator connection (terminal AM).
Isolated from terminals SD and SE. Do not connect this
terminal to the ground.
A
B
C
Alarm output
1 contact output which indicates that the
protective function of the inverter is
activated to stop output. 230V 0.3A AC,
30V 0.3A DC. No conduction across B-C
(conduction across A-C) when alarm
(error) state.
Conduction across B-C (no conduction
across A-C) when normal. (*6)
Open collector
RUN Inverter running
Low when the inverter output frequency
is the starting frequency or higher
(factory-set to 0.5Hz and changeable),
and High during stop or DC injection
brake operation (*2). Permissible load
24V 0.1A DC
The terminal
function
changes with the
setting of output
terminal function
selection
(Pr. 64, Pr. 65).
(*5)
SE
Open collector
common
Common terminal for inverter running terminal RUN.
Isolated from terminals 5 and SD.
Pulse
FM
<Japanese>
For meter
Factory setting of output item:
Frequency
Permissible load current 1mA
1440 pulses/s at 60Hz
Output signals
Indicator
Analog
AM
<NA, EC>
Analog signal
output
One selected from output
frequency and motor
current is output.
The output signal is
proportional to the
magnitude of each
monitoring item.
Factory setting of output item:
Frequency
Output signal 0 to 5VDC
Permissible load current 1mA
Communication
RS-485
connector
(*3)
Using the parameter unit connection cable (FR-CB201 to
205), the parameter unit (FR-PU04) can be connected.
Communication operation can be performed using RS-485.
*1. Do not connect terminals SD and PC each other or to the ground.
For sink logic, terminal SD acts as the common terminal of contact input. For source
logic, terminal PC acts as the common terminal of contact input.
*2. Low indicates that the open collector output transistor is on (conducts). High indicates
that the transistor is off (does not conduct).
*3. Compatible with only the type having the RS-485 communication function. For details,
refer to the separately available instruction manual (detailed).
*4. RL, RM, RH, RT, AU, STOP, MRS, OH, REX, JOG, RES, X14, X16, (STR) signal
selection
*5. RUN, SU, OL, FU, RY, Y12, Y13, FDN, FUP, RL, LF, ABC signal selection
*6. For compatibility with the European Directive (Low Voltage Directive), the operating
capacity of relay output (A, B, C) should be 30V, 0.3A DC.