5.2 Adjustment (Calibration) of the Frequency Meter
(Indicator)
Changing example Deflecting the meter (analog indicator) to full-scale (across
FM-SD: 1mA, across AM-5: 5V) at the preset frequency of
60Hz. (Refer to page 22 for frequency setting)
POINT
The calibration parameters "C1" can be made to be read by setting "1" (extended
function parameter valid) in Pr. 30 "extended function display selection".
Set the value of the calibration parameter C1 "FM (AM) terminal calibration".
MODE
4.
5.
Press the key to enable setting.
SET
SET
3.
SET
8.
SET
Flicker ... Parameter setting complete!!
SET
6.
RUN
PU
EXT
RUN
RUN
+
-
7.
1.
MODE
Pr. 30 must be set to "1".
(For details, refer to steps 3 to 6
on page 25.)
2.
Turn the setting dial to show
" "
.
Operation
Display
Press the key to show
SET
" "
.
The parameter
number read
previously
appears.
By turning the
setting
dial , you can read another parameter.
SET
Press the key to return to the " " indication (step 3).
SET
Press the key twice to show the next parameter ( ).
Press the key to choose the
parameter setting mode.
Turn the
setting
dial until the
calibration parameter C1 "FM (AM)
terminal calibration" appears.
need not be connected.)
Press the key.
Setting is complete.
Turn the
setting
dial to
adjust the indicator needle
to the desired position.
Analog indicator
In PU operation mode
If the inverter is at a stop, press the
key to start it.
(The motor
Remarks
Depending on the set value, it may take some time for the needle to move.
If "1" is set in Pr. 30 "extended function display selection", the calibration parameter
C1 "FM (AM) terminal calibration" can also be set in the external operation mode.
POINT
By setting the Pr. 54 "FM (AM) terminal function selection" value, preset Pr. 55
"frequency monitoring reference" or Pr. 56 "current monitoring reference" to the
running frequency or current value at which the output signal is 1440 pulses/s (5V).
At 1440 pulses/s (5V), the meter generally deflects to full-scale.