7. ERRORS AND PROTECTIVE FUNCTIONS
7.1 About Errors (Definitions)
When an alarm occurs in the inverter, the protective function is activated to bring
the inverter to an alarm stop and the PU display automatically changes to any of
the following error (alarm) indications.
For details, refer to the instruction manual (detailed) which is separately available.
(1) Major failures
Control Panel
Indication
Function Name Definition
(OC1)
Overcurrent cut-off during
acceleration
The inverter output current rose to or
above about 200% of the rated inverter
current during acceleration.
(OC2)
Overcurrent cut-off during
constant speed
The inverter output current rose to or
above about 200% of the rated inverter
current during constant-speed operation.
(OC3)
Overcurrent cut-off during
deceleration
The inverter output current rose to or
above about 200% of the rated inverter
current during deceleration.
(OV1)
Regenerative overvoltage
cut-off during acceleration
Excessive regenerative energy or surge
voltage occurred during acceleration.
(OV2)
Regenerative overvoltage
cut-off during constant
speed
Excessive regenerative energy or surge
voltage occurred during constant speed.
(OV3)
Regenerative overvoltage
cut-off during deceleration
or stop
Excessive regenerative energy or surge
voltage occurred during deceleration or
stop.
(THM)
Motor overload cut-off
(Electronic thermal
overcurrent protection) (*1)
Overload or reduced cooling capability
during low-speed operation
Protection from burning due to motor
temperature rise
(THT)
Inverter overload cut-off
(Electronic thermal
overcurrent protection) (*1)
Current more than 150% of the rated
output current flew and overcurrent shut-off
did not occur.
Output transistor protection from overheat
(FIN)
Fin overheat Temperature rise of the heat sink.
(GF)
Start-time output side
ground fault overcurrent
protection (*2)
Ground fault occurred on the inverter's
output side.
(OHT)
External thermal relay (*3)
External thermal relay provided for
protection from overheat was actuated
(contact open).
(OLT)
Stall prevention (overload)
Stall prevention was activated to drop the
running frequency to 0. (OL appears while
stall prevention is activated.)
(OPT)
Communication error
Communication errors occurred
consecutively more than the permissible
number of retries when the RS-485
connector is used and communication
parameter n5 = "- - -".
RS-485 communication error occurred.
Communication was broken for a period
set in communication parameter n6.
(Only for the type with RS-485 function.)
(PE)
Parameter error Error occurred in the parameter stored.