Mitsubishi City Multi PMFY-P.VBM-E Specifications Page 38

  • Download
  • Add to my manuals
  • Print
  • Page
    / 69
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 37
Appearance
Model line up
LGH-15~100RX5-E
LGH-150 / 200RX5-E
Page74
LOSSNAY
In addition to the automatic damper open/close function,
open/close control via external devices is now possible,
delivering a By-pass ventilation system that is
suitable to the installed environment.
.
Temperature sensor
.
Humidity sensor
.
Timers
"By-pass" operation
New function: "By-pass" Ventilation External Control Setting
* When the outdoor air tempereture drops lower than 8˚C
it changes to the heat
exchange ventilation
. (Display of the remote controller does not change.)
* In the case of
“By-pass” ventilation, the supply air temperature slightly rises more
than the outside air temperature because of the heat effect around the ducts or the
unit motors.
Automatic ventilation setting
The automatic damper mode automatically provides
the correct ventilation for the conditions in the room.
The following shows the effect “By-pass” ventilation will
have under various conditions.
1. Reduces cooling load
If the air outside is cooler than the air inside the
building during the cooling season (such as early
morning or at night), “By-pass” ventilation will draw
in the cooler outside air and reduce the cooling load
on the system.
2. Night purge
“By-pass” ventilation can be used to release hot air
from inside the building that has accumulated in
buildings a business district during the hot summer
season.
3. Office equipment room cooling
During cold season, fresh air can be drawn in and used
as is to cool rooms where the temperature has risen
due to the use of office equipment.
Establish the wire connection by inserting the optional
remote display adaptor (PAC-SA88HA-E) in the connector
CN16 (Ventilation mode selector).
With SW1 is “ON”, the ventilation mode of LOSSNAY is
changed to the By-pass ventilation regardless of the
setting on the remote controller.
Control devices (example)
SW1
CN16
SW1: By-pass ventilation operation switch
(When closed: For By-pass ventilation operation)
Remote display adaptor
(Optional) PAC-SA88HA-E
Brown 1
Red 2
Green 5
Not used. Insulate completely
LOSSNAY
control board
Fan speed/
entilation
mode selection
Max wiring length 10 m
Damper
LOSSNAY core
Fresh air
Supply air
Exhaust air
Return air
New Remote Controller PZ-60DR-E
A new remote controller for the RX5 series is now available. In addition to boosting the energy conservation perfor-
mance of the main unit, the remote controller features a variety of new functions which also pursue additional energy
conservation.
The appearance of the remote controller conforms to Mitsubishi air conditioner interface design standards.
Functions that were set using Dip-
Switch on the LOSSNAY main unit
can now be configured as needed
using the new remote controller.
This eliminates the need to crawl un-
der the eaves to change operation
settings.
Also, a newly adopted dot matrix dis-
play provides much more informa-
tion, making it easy to check mainte-
nance indications, operation status
display, and explanations required
when configuring settings.
Dot matrix display
Button
FILTER button
"Extra Low" fan speed button
OPERATION button
ON/OFF button
Function selector button
Set time buttons
Back Ahead
OPERATION buttons
Back Ahead
Fan speed Adjustment button
CLEAR button
Timer ON/OFF (DAY) button
Timer MENU (MONITOR/SET) button
Return button
Orange 3
Yellow 4
Page73
Indoor unit
Page view 37
1 2 ... 33 34 35 36 37 38 39 40 41 42 43 ... 68 69