Maintenance equipment
Maintenance cycle [Note that maintenance cycle does not mean guarantee period.]
The following tables are applicable when using equipment under the conditions below.
Normal use without frequent START/STOPs (The number of START/STOPs is assumed to be less than 6 times
per hour in normal use.)
Operating hours are assumed to be 10 hours per day/2500 hours per year.
Under the following conditions, equipment may not be able to be used at all, or the maintenance cycle and
replacement cycle of equipment may need to be shortened.
When using equipment in high temperature and humidity or in rapid changes in temperature and humidity
When using equipment in a big electric change of power voltage, frequency, and waveform distortion (They
cannot be used outside of acceptable range.)
When using equipment installed in a place where there is a lot of vibration
When using equipment in the air with hazardous gas or oil mist as well as dust, salinity, and sulfur dioxide/
hydrogen sulfide
When using equipment with frequent START/STOP or long operating hours
Table 1. Maintenance cycle
Table 2. Replacement cycle
Major components
Checking cycle
Maintenance cycle
Compressor 20,000 hours
Motor
20,000 hours
(Fan, Louver, drain pump)
Bearing
1 year
15,000 hours
Electric board 25,000 hours
Heat exchanger 5 years
Major components
Checking cycle
Maintenance cycle
Expansion valve 20,000 hours
Valve
20,000 hours
(solenoid valve, four-way valve)
1 year
Sensor
5 years
(thermistor, presser sensor)
Drain pan 8 years
Sudden unpredictable accident may occur even if check-up is performed.
Replacement cycle of consumable components
[Note that replacement cycle does not mean guarantee period.]
Major components
Checking cycle
Replacement cycle
Long-life filter 5 years
High-performance filter 1 year
Fan belt
1 year
5,000 hours
Smoothing capacitor 10 years
Fuse 10 years
Crank case heater 8 years
Note1 This table shows major components. Refer to the maintenance contract for details.
Note2 This maintenance cycle shows a period in which products are expected to require no maintenance. Use this cycle for planning maintenance (budgeting the
maintenance expense etc.) Checking/ Maintenance cycle may be shorter than the one on this table depending on the contents of maintenance check
contract.
Note1 This table shows major components. Refer to the maintenance contract for
details.
Note2 This replacement cycle shows a period in which products are expected to
require no replacements. Use this cycle for planning maintenance
(budgeting expenses for replacing equipments etc.)
Page134
Optional parts
>>For PUHY series
OPTIONAL PARTS FOR OUTDOOR UNITS
OPTIONAL PARTS FOR CONTROL
Description Remarks Model
Branch pipe (Joint)
Branch pipe (Header)
200 or below (Total capacity of indoor unit)
201-400 (Total capacity of indoor unit)
401-650 (Total capacity of indoor unit)
The 1st branch of P450~P650
651 or above (Total capacity of indoor unit)
The 1st branch of P700~P1250
For 4 branches
For 8 branches
For 10 branches
Twinning kit
Model Description
PAC-SE41TS-E
PAC-SE55RA-E
PAC-SA88HA-EP
PAC-SA89TA-EP
PAC-SC37SA-E
PAC-SC36NA-E
PAC-SF46EPA
LMAP02
PAC-YG11CDA
PAC-YG31CDA
BAC-HD150
Remote Sensor for A/J/K/M-Net Control
Remote ON/OFF adaptor for Indoor Unit
Remote Display Adaptor for Indoor Unit
Timer Adaptor for remote controller
Output signal connector
Input signal connector
Transmission booster
Air conditioner interface
Electric amount count software
BAC net
R
interface
BAC net
R
and M-NET adapter
Note : Indoor unit capacities: the capacity of an indoor unit is the same as the number used for its type identification.
CMY-Y102S-G2
CMY-Y102L-G2
CMY-Y202-G2
CMY-Y302-G2
CMY-Y104-G
CMY-Y108-G
CMY-Y1010-G
OPTIONAL EQUIPMENT FOR BC CONTROLLER
BC Controller Model
CMB-P104V-G, GB
CMB-P105V-G
CMB-P106V-G
CMB-P108V-G, GA, GB
CMB-P1010V-G, GA
CMB-P1013V-G, GA
CMB-P1016V-G, GA, HA, HB
CMY-R160-J
>>For PUMY-P100 , P125 , P140 VHM
Description Model
Branch Pipe (2 Branch)
Header
Header
Drain Socket
Centralized Drain Pan
Port Connector (
ø9.52 ø12.7 )
Port Connector (
ø15.88 ø19.05)
Air Protect Guide ( 2 pcs required )
CMY-Y62-G-E
CMY-Y64-G-E
CMY-Y68-G-E
PAC-SG61DS-E
PAC-SG64DP-E
PAC-SG73RJ-E
PAC-SG75RJ-E
PAC-SH63AG-E
>>For PURY series
Description RemarksModel
Branch pipeJunction pipe kit
Branch pipe (Joint)
200 or below (Total capacity of indoor unit)
201-400 (Total capacity of indoor unit)
401-650 (Total capacity of indoor unit)
The 1st branch of P450~P650
Twinning kit
CMY-R100VBK
CMY-R200VBK
For PURY-P450~P650 / EP400~EP600YSHM
For PURY-P700~P800YSHM
CMY-Y102S-G2
Note : Indoor unit capacities: the capacity of an indoor unit is the same as the number used for its type identification.
CMY-Y102S-G2
CMY-Y102L-G2
CMY-Y202-G2
CMY-Y100VBK2
CMY-Y200VBK2
CMY-Y300VBK2
For PUHY-P500~P650 / EP400~EP650YSHM
For PUHY-P700~P900YSHM
For PUHY-P950~P1250 / EP700~EP900YSHM
>>For PUHY-HP series
Description Remarks Model
Branch pipe (Header)
Twinning kit
The 1st branch of P400,P500
For 4 branches
For 8 branches
For 10 branches
For PUHY-HP400,HP500YSHM-A(BS)
Branch pipe (Joint)
Note : Indoor unit capacities: the capacity of an indoor unit is the same as the number used for its type identification.
CMY-Y102S-G2
CMY-Y102L-G2
CMY-Y202-G2
CMY-Y104-G
CMY-Y108-G
CMY-Y1010-G
CMY-Y100VBK2
200 or below (Total capacity of indoor unit)
201-400 (Total capacity of indoor unit)
401-650 (Total capacity of indoor unit)
Model Description
PAC-YG10HA
PAC-YG50ECA
PAC-SC51KUA
PAC-YG81TB
PAC-YG83UTB
PAC-YG85KTB
PAC-YG71CBL
External input/output adapter for AG-150A
Expansion controller for AG-150A
Power supply unit for AG-150A / GB-50A
Mounting attachment B type for AG-150A wall-mount installations
Electric box for AG-150A wall-embed installations
Mounting attachment A type for AG-150A/PAC-SC51KUA wall-mount installations
Black surface cover for AG-150A
>>For PQHY series
Description RemarksModel
Branch pipe (Joint)
Branch pipe (Header)
Twinning kit
CMY-Y102S-G2
CMY-Y102L-G2
CMY-Y202-G2
CMY-Y302-G2
CMY-Y104-G
CMY-Y108-G
CMY-Y1010-G
CMY-Y100VBK2
200 or below (Total capacity of indoor unit)
201-400 (Total capacity of indoor unit)
401-650 (Total capacity of indoor unit)
The first branch of P400-P600
651 or above (Total capacity of indoor unit)
For 4 branches
For 8 branches
For 10 branches
For PQHY-P400-P600YSHM-A
>>For PQRY series
Description RemarksModel
Branch pipe (Joint)
Twinning kit
CMY-Y102S-G2
CMY-Y102L-G2
CMY-Y202-G2
CMY-Q100VBK
200 or below (Total capacity of indoor unit)
201-400 (Total capacity of indoor unit)
401-650 (Total capacity of indoor unit)
The first branch of P400-P600
For PQRY-P400-P600YSHM-A
Page133