Mitsubishi PU-5TJSA Service Manual Page 27

  • Download
  • Add to my manuals
  • Print
  • Page
    / 52
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 26
27
2-5 Test run
The unit starts the test run by pressing both the UP and DOWN buttons simultaneously for more than two seconds during
lamp ON or the unit OFF.
The test run automatically stops in 2 hours.
Set temperature is not displayed during test run.
To cancel the test run, press the POWER ON/OFF button.
<Initial setting>
The units are set as follows by the factory.
1) Initial operation mode: FAN 3) Swing louver : OFF
2) Fan speed : LOW 4) Set temperature: 28°C
2-6 Emergency operation
When the remote controller or microprocessor malfunc-
tions and no other trouble exists, emergency operation
is available by setting the dipswitch on the indoor con-
troller board.
[Check items]
! Make sure the compressor and the fans are running
normally.
@ Locate the trouble with the self-doagnostic function. If
the self-diagonostic function indicates that the protec-
tion device (such as coil frost protection)is function-
ing, the sources must be removed before attempting
emergency operation.
Emergency operation ON/OFF is activated not with
the remote controller but with the circuit breaker.
[Emergency operation procedure]
! Cooling operation is available by setting the dipswitch
SW3 1 and 2 ON and 3 OFF on the indoor con-
troller board.
INDOOR CONTROLLER BOARD
SW3
TIMER
w
2-7 Auto Restart function
Unit can be start / stop by turning the breaker ON / OFF.
! Cutting the JR06 on the indoor board.
Unit can be start / stop using a remote controller. Only If the unit was already being operated before power off, the unit resta
automatically as soon as power is back.
@ To start emergency operation, turn the outdoor sidecircuit breakerON first, and then the indoor side circuit breaker ON.
# During emergency operation, the indoor fan runs on HIGH speed, the compressor runs continuously, and the louver
stops.
When the drain pump is attached, it works in emergency operation.
$ Thermostat will not function.
% Do not use emergency cooling operation for more than 10 hours, as the indoor coil may freeze.
w If the self-diagnostic function shows a drain pump malfunction, do not attempt emergency operation, as the drain may
overflow.
JR06 Auto restart
Available Not effective
Not available Effective
@ Short all the CN2 on the indoor board.
Unit can not be start/ stop using remote controller.
Unit will restart automatically whether the unit is
operated or stopped when the power is cut off.
1
2CN2
3
ORN
BRN
RED
Optional timer adapter
PAC-SA89TA-E
I.B.