4. Set the address number (from SW1-1 to SW1-6) in
the dipswitch when a centralized remote controller is
being used.
The address is the control number of each unit in the
centralized control system.
As the address serves as a time-delay device as
well, sequential starts (all units are triggered collec-
tively by one single ON instruction)must be set with
different address numbers (greater than 0) for each
adapter.
4.TIMER ADAPTER
This adapter is needed for system control and for operation via external contacts.
Adaptor
200~240V AC
3-core cable 5-core cable
52
To program timer or
centralized remote
controller
Fig.3
CN30 CN50
CN51
Remote controller Indoor unit
Max. length of each calbe is 10m.
65
230
22
15 15
86 70
35
27
3holes
15
hole
40 80 40 27
18
4Fixing screw holes
5.5
95
220
22
35
120
12
30
200
2 2holes 2.9
74
7
8
Fig. 4
(Unit : mm)
ON
SW1
Levers No. 1-6 can set the following addresses respectively
with binary notations.
Address
Toggle
32
No.6 ON
16
No.5 ON
8
No.4 ON
4
No.3 ON
2
No.2 ON
1
No.1 ON
10
987654321
ON
10
987654321
ON
10
987654321
ON
10
987654321
(Ex.1) 3 = 2 + 1 (Ex.2) 9 = 8 + 1 (Ex.3) 15 = 8 + 4 + 2 + 1
Part No. PAC-SA89TA-E
(3) Connection from adaptor
5. Dimensions
ORN 1
2
3
BRN
RED