9 WIRING SPECIFICATIONS
9-1. FIELD ELECTRICAL WIRING (power wiring specifications)
1
2
S1
S2
S3
S1
S2
S3
Indoor/outdoor
unit connection
cable
Indoor
unit
Unit
power
supply
Outdoor
unit
Remote
controller
L
B
N
B Earth leakage breaker
C wiring circuit breaker or
isolating switch
C
B
B Earth leakage breaker
C wiring circuit breaker or
isolating switch
C
L
N
1
2
1
2
S1
Indoor
unit
S2
S3
S1
S2
S3
S1
S2
S3
Unit
power
supply
Indoor/outdoor
unit connection
cable
Indoor
unit
Outdoor
unit
Remote
controller
B
B Earth leakage breaker
C wiring circuit breaker or
isolating switch
C
1
2
1
2
1
2
S1
S2
S3
S1
S2
S3
S1
S2
S3
S1
S2
S3
Indoor/outdoor
connection cable
Indoor
unit
Unit
power
supply
Indoor
unit
Indoor
unit
Outdoor
unit
Remote
controller
L
N
1:1 system Electrical wiring Synchronized twin and triple system Electrical wiring
Synchronized twin
Synchronized triple
Outdoor unit model
Outdoor unit power supply
Outdoor unit input capacity *1
Main switch (Breaker)
Outdoor unit power supply
Outdoor unit power supply earth
Indoor unit-Outdoor unit *2
Indoor unit-Outdoor unit earth *2
Remote controller-Indoor unit *3
Outdoor unit L-N (single)
*4
Outdoor unit L1-N, L2-N, L3-N (3 phase)
Indoor unit-Outdoor unit S1-S2 *4
Indoor unit-Outdoor unit S2-S3 *4
Remote controller-Indoor unit *4
Wir
ing
Wire No. o
size (mm
2
)
Circuit rating
RP35, 50V RP60, 71V RP100, 125V RP140V RP100, 125, 140Y
~/N (single), 50 Hz, ~/N (single), 50 Hz, ~/N (single), 50 Hz, ~/N (single), 50 Hz, 3N ~ (3phase), 50 Hz,
230 V 230 V 230 V 230 V 400 V
16 A 25 A 32 A 40 A 16 A
2 o Min. 1.5 2 o Min. 2.5 2 o Min. 4 2 o Min. 6 4 o Min. 1.5
1 o Min. 1.5 1 o Min. 2.5 1 o Min. 4 1 o Min. 6 1 o Min. 1.5
3 o 1.5 (Polar) 3 o 1.5 (Polar ) 3 o 1.5 (Polar) 3 o 1.5 (Polar) 3 o 1.5 (Polar)
1 o Min. 1.5 1 o Min. 1.5 1 o Min. 1.5 1 o Min. 1.5 1 o Min. 1.5
2 o 0.3 (Non-polar) 2 o 0.3 (Non-polar ) 2 o 0.3 (Non-polar) 2 o 0.3 (Non-polar) 2 o 0.3 (Non-polar)
AC 230 V AC 230 V AC 230 V AC 230 V AC 230 V
AC 230 V AC 230 V AC 230 V AC 230 V AC 230 V
DC 24 V DC 24 V DC 24 V DC 24 V DC 24 V
DC 12 V DC 12 V DC 12 V DC 12 V DC 12 V
*1.
The breaker shall be provided to ensure disconnection of all active phase conductor of the supply.
A breaker with at least 3 mm contact separation in each poles shall be provided. Use earth leakage beaker(NV).
*2. Refer to 9-3.
*3. The 10 m wire is attached in the remote controller accessory.
*4. The figures are NOT always against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device .
Notes: 1. Wiring size must comply with the applicable local and national code..
2. Power supply cables and Indoor/Outdoor unit connecting cables shall not be lighter than polychloroprene sheathed flexible cable.
3. Install an earth longer than other cables.
Warning:
In case of A-control wiring,
there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between
power line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals
when the power is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.
(Design 60245 IEC 57)
S1
S2
S3
S1
S2
S3
A-Control
Outdoor Unit
3 poles isolator
230V
Single phase
Isolator
A-Control
Indoor Unit
OC374C--2.qxp 08.2.22 8:16 AM Page 32