Mitsubishi FR-S500 Instruction Manual Page 120

  • Download
  • Add to my manuals
  • Print
  • Page
    / 191
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 119
111
2
2
.11.3 Motor primary resistance
Generally this parameter need not be set. At the factory setting of "- - -", the
standard motor constant of the motor capacity set in Pr. 98 (including that of the
constant-torque motor) is used.
Parameter Name
Factory
Setting
Setting
Range
Remarks
99
Motor primary
resistance
- - -
0 to 50
,
- - -
Setting is enabled when Pr. 30 = "1"
Related parameters
Applied motor setting
Pr. 71 "applied motor" (refer to page 93)
Automatic torque boost selection
Pr. 98 "automatic torque boost selection (motor capacity)"
(refer to page 109)
2
.12 Calibration Parameters
2
.12.1 Meter (frequency meter) calibration
(Japanese version)
By using the control panel or parameter unit, you can calibrate a analog meter
connected to terminal FM to full scale deflection.
Terminal FM provides the pulse output. By setting the calibration parameter
C1, you can use the parameter to calibrate the analog meter connected to the
inverter without providing a calibration resistor.
Parameter Name Factory Setting Setting Range Remarks
C1 (900)
FM terminal
calibration
——— ———
Setting is enabled when
Pr. 30 = "1"
The parameter number in parentheses applies to when the parameter unit (FR-PU04) is
used.